FIR13-00043
| INSP-Sprinkler Rough-in | 2/28/2013 | 3/1/2013 | 3/1/2013 4:01:26 PM | A | CANC |
|
|
Overbooked. Rescheduled for monday. I spoke to Mike with Shilo about this.
|
FIR12-00750
| INSP-Sprinkler Rough-in/Hydro | 3/1/2013 | 3/1/2013 | 3/1/2013 3:56:41 PM | A | CANC |
|
|
Piping was not ready for inspection when I stopped at the project the first time. I could not make it back due to schedule when the piping was ready. Per Sam and I's discussion this will be rescheduled for monday.
|
FIR12-00662
| INSP-Final Inspection | 2/28/2013 | 3/1/2013 | 3/1/2013 3:44:26 PM | P | PASS |
|
|
Permit finaled.
|
FIR12-00715
| INSP-Final Inspection | 2/28/2013 | 3/1/2013 | 3/1/2013 3:43:44 PM | P | PASS |
|
|
Permit finaled. THe zone 4 description at central station had to be changed but was done and retested while I waited.
|
BLD12-00343
| FIRE-Final Inspection | 3/1/2013 | 3/1/2013 | 3/1/2013 3:21:30 PM | P | PART |
|
|
A temporary occupancy was given with scott arellanos permision until the additional smoke alarm is installed in the vestibule between the staff sleeping rooms as per the city approved fire alarm plans. Once installed this device will need to be tested. I also need the final paper work. All other life safety items are ok.
|
FIR12-00711
| INSP-Final Inspection | 2/27/2013 | 3/1/2013 | 3/1/2013 3:20:16 PM | P | PART |
|
|
A temporary occupancy was given with scott arellanos permision until the additional smoke alarm is installed in the vestibule between the staff sleeping rooms as per the city approved fire alarm plans. Once installed this device will need to be tested. I also need the final paper work.
|
FIR13-00067
| INSP-Final Inspection | 2/28/2013 | 3/1/2013 | 3/1/2013 3:17:42 PM | P | PASS |
|
|
Permit finaled. Hood suppression system functioned correctly. The manual pull seemed harder to pull than others. I notified the contractor that per IFC 904.11.1 the max force to operate is 40 lbs.
|
FIR12-00637
| INSP-Final Inspection | 2/28/2013 | 3/1/2013 | 3/1/2013 3:13:48 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00070
| FIR-Aging Inspection | 3/1/2013 | 3/1/2013 | 3/1/2013 10:37:48 AM | A | PART |
|
|
The underground supply piping from the point of connection to the building foundation is ok to cover.
|
BLD12-03002
| FIRE-Final Inspection | 2/28/2013 | 3/1/2013 | 3/1/2013 10:21:15 AM | A | PART |
|
|
A temporary occupancy was given with scott arellano's permission. The existing fire alarm system needs to be extended into this new corridor. During my walk through of the existing building I found what appears to be non-compliant audio/visual portion of a fire alarm system. I found some rooms with smoke detectors, some at what appear to be fire doors. I also found strobes overspaced in one room and another with a ceiling mounted horn. I spoke to the superintendant, Ron, about contacting tim woodard in plan review to get the fire dept. involved with this.
|
FIR12-00662
| INSP-Final Inspection | 2/28/2013 | 3/1/2013 | 2/28/2013 3:51:57 PM | A | CANC |
|
|
Please call 45 minutes prior to inspection. Mark is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR12-00637
| INSP-Sprinkler Rough-in/Hydro | 2/28/2013 | 3/1/2013 | 2/28/2013 9:28:42 AM | P | CANC |
|
|
Trent Bice is contact at ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
|
FIR12-00637
| INSP-Final Inspection | 2/28/2013 | 3/1/2013 | 2/28/2013 9:18:27 AM | A | CANC |
|
|
Please contact Trent Bice at ###-#### Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
|