Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00795 INSP-Sprinkler Rough-in2/29/20163/1/20163/1/2016 4:27:45 PMPFAIL
Rough to cover inspection performed, cover is not approved, numorous hangers are overspaced, hanger spacing needs to be corrected throughout entire building before cover is approved.
BLD16-00204 FIRE-Final Inspection3/1/20163/1/20163/1/2016 3:58:08 PMPPART
Fire sprinkler has current inspection tag, fire extinguishers have current inspection tags. Exit lights have been repaired and are now functional. Emergency egress lighting has been repaired and are now functional. Final item for repair is the smoke detector missing located in the basement and inspection of smoke curtian operation on each floor for the elevator.
FIR15-00865 INSP-Sprinkler Rough-in2/29/20163/1/20163/1/2016 2:45:55 PMPFAIL
End of line seismic bracing missing on northwest branchlines.
FIR15-00865 INSP-Supply line flush2/29/20163/1/20163/1/2016 2:44:03 PMPDONE
Underground main supply line flush complete
FIR15-00793 INSP-Sprinkler Rough-in3/1/20163/1/20163/1/2016 1:50:46 PMPPASS
Rough to cover inspection performed on 18NOV2015 for underground piping, underground was approved for cover at that inspection.
FIR15-00633 INSP-Final Inspection2/29/20163/1/20163/1/2016 11:52:36 AMAFAIL
Final inspection cannot be completed, missing fire sprinkler head for attached storage area located on the east side of building (there is an open outlet in the southeast room that is for the fire sprinkler head in the storage area) The underground flush has not been accomplished. No hydrostatic test has been performed for the overhead fire sprinkler piping. At time of inspection there is was no exterior bell for the fire department connection. Exterior tamper switch and water flow switch will need to be tested during the fire alarm inspection (Fire alarm pemit number is FIR16-00018). No tamper switches are installed on the fire sprinkler backflow, tamper switches need to be installed. Fire sprinkler headbox needs to be installed in fire sprinkler riser room. Fire sprinkler backflow needs to tested by a licensed backflow tester. Loose/pulled free hangers will need to be repaired. City approved drawings were not on site at time of final inspection, contractor will need to provide city approved drawings for next inspection. The door to the riser room needs to be labeled "FIRE SPRINKLER RISER ROOM"
FIR15-00819 INSP-Final Inspection2/26/20163/1/20163/1/2016 10:10:39 AMAPASS
Final fire alarm inspection passed/complete