BLD19-00582
| FIRE-Final Inspection | 3/1/2019 | 3/1/2019 | 3/1/2019 4:14:44 PM | P | FAIL |
|
|
Service or replace exit signs and emergency lighting that is inoperable as discussed. Provide annual inspections for fire extinguishers, last inspection for extinguishers was 2016. Fire sprinkler system has a current inspection tag. Preaction fire sprinkler system riser is still in place but has been disconnected and removed from service, fire sprinkler piping on the preaction system has been converted to a wet system but valve trim is still in place. Change pendant fire sprinkler that is to close to wall to a vertical sidewall to be code compliant.
call ahead // Nick Phone #: ###-####
|
BLD17-04425
| FIRE-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 3:26:21 PM | A | CANC |
|
|
Rescheduled per conversation with point of contact.
Brandon Phone #: ###-####
|
BLD17-04413
| FIRE-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 3:26:06 PM | A | CANC |
|
|
Rescheduled per conversation with point of contact.
Brandon Phone #: ###-####
|
FIR19-00113
| INSP-Sprinkler Rough-in | 3/1/2019 | 3/1/2019 | 3/1/2019 3:22:38 PM | P | PASS |
|
|
Rough in inspection for scope of work complete.
tom Phone #: ###-####
|
BLD17-04483
| FIRE-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 2:33:00 PM | A | FAIL |
|
|
Provide emergency exit discharge illuminatoin as stated in note number 7 of the building permit fire code review comments. Northeast exit door swings the wrong direction, swing is not with the path of travel, city approved drawings show door swinging with the exit path of travel.
7###-#### Kai
|
FIR19-00108
| INSP-Final Inspection | 3/1/2019 | 3/1/2019 | 3/1/2019 2:03:11 PM | P | PASS |
|
|
Final fire sprinkler inspection for scope of work complete.
Tom Small Phone #: ###-#### Inspection requested via web by Nathan Stenquist
|
FIR18-00908
| INSP-Sprinkler Rough-in | 2/28/2019 | 3/1/2019 | 3/1/2019 2:02:38 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping above drop in ceiling complete, approved for cover.
Please Call Roy Nelsen for contact. Phone #: ###-#### Inspection requested via web by Daniel Buccino
|
FIR18-00930
| INSP-Sprinkler Rough-in/Hydro | 2/28/2019 | 3/1/2019 | 3/1/2019 2:01:50 PM | P | DONE |
|
|
Hydrostatic test for canopy dry system witnessed, no pressure loss observed.
zack Phone #: ###-####
|
BLD19-00466
| FIRE-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 1:10:02 PM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
Lina Phone #: ###-####
|
BLD18-02512
| FIRE-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 12:02:32 PM | A | FAIL |
|
|
Fire alamrs did not pass inspection, no life fire safety inspection was performed. Fire alarms must be inspected and passed before life fire safety inspection can be performed.
Pete Phone #: ###-####
|
BLD18-01753
| FIRE-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 12:01:15 PM | A | FAIL |
|
|
Permit shows being under review at time of this request, no inspection was performed. Fire alarms and fire sprinkler did not pass inspection. Tom Phone #: ###-####
|
FIR18-00852
| INSP-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 12:00:04 PM | P | FAIL |
|
|
Inspection for rough in was failed, reference notes provided under rough in inspection.
Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR18-00852
| INSP-Sprinkler Rough-in/Hydro | 2/28/2019 | 3/1/2019 | 3/1/2019 11:59:02 AM | A | FAIL |
|
|
Add head in closet on 5 as discussed. City approved drawings do not show stair opening between 3 and 4, no head under stairs, could not verify space under landing, appears to be a combustible concealed space. Close spaced sprinkler heads may be required between levels.
Rough to cover Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR18-00538
| FIR-Aging Inspection | 3/1/2019 | 3/1/2019 | 3/1/2019 11:56:06 AM | P | PASS |
|
|
Final inspection for underground supply complete.
can you final this yet?
|
FIR18-00825
| INSP-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 11:55:23 AM | A | FAIL |
|
|
Drawings provided did not ahow notification in tenant space, provide correct city approved drawings.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00714
| INSP-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 11:54:28 AM | A | FAIL |
|
|
Notated city approved drawings areas that need corrected, no alarms were activated due to deficiencies.
Contact is Dirk Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00214
| INSP-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 11:51:56 AM | A | FAIL |
|
|
Notated city approved drawings areas that need corrected, no alarms were activated due to deficiencies.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR18-00213
| INSP-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 11:51:28 AM | A | FAIL |
|
|
Notated city approved drawings areas that need corrected, no alarms were activated due to deficiencies.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD18-00945
| FIRE-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 10:32:41 AM | A | FAIL |
|
|
Fire alarm permit (FIR18-00644) associated with this project has not been inspected or finaled, fire alarm inspection needs to be completed and finaled before life fire safety inspection can be perfromed.ron Phone #: ###-####
|
BLD18-00887
| FIRE-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 10:30:16 AM | A | PASS |
|
|
Final life fire safety inspection complete.
Request for Fire, life, Safety in conjunction with final sprinkler, alarm test, as scheduled by Larson Fire, Webster Alarm . Best access usually in alley. Thank you. Phone #: ###-#### Inspection requested via web by Gary Band
|
FIR18-00686
| INSP-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 10:29:41 AM | A | PASS |
|
|
Final fire sprinkler inspection complete.
Ron Phone #: ###-####
|
FIR18-00717
| INSP-Final Inspection | 2/28/2019 | 3/1/2019 | 3/1/2019 10:29:04 AM | A | PASS |
|
|
Final fire alarm inspection to include as-builts complete.
Buck Phone #: ###-####
|