FIR99-00670
| INSP-Sprinkler Rough-in/Hydro | 3/9/2000 | 3/10/2000 | 3/10/2000 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 03/09/2000 at 15:49:45. Contact: ###-####. Ok on underground and above ground hydro test. 3/14/00 11:53:37 AM
|
BLD99-03704
| BLD-Final | 3/10/2000 | 3/10/2000 | 3/10/2000 12:00:00 AM | A | FAIL |
|
|
Reinsp. fail fire alarms system.
|
BLD99-01785
| FIRE-Final Inspection | 3/6/2000 | 3/10/2000 | 3/10/2000 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 03/06/2000 at 13:25:07. Contact: ###-####. Alarm test fail reprogram 2 floor switches on dry pipe systems & tamper switches on ostey valves. 3/14/00 11:22:30 AM
|
BLD98-01674
| FIRE-Supply Line Hydro | 3/10/2000 | 3/10/2000 | 3/10/2000 12:00:00 AM | P | PART |
|
|
terry nelson ###-#### Ok on underground & above ground hydro tests. 3/14/00 11:21:59 AM
|
FIR99-00640
| INSP-Final Inspection | 3/10/2000 | 3/10/2000 | 3/10/2000 12:00:00 AM | P | FAIL |
|
|
don ###-#### pager Alarm test fail reprogram 2 floor switches on dry pipe systems & tamper switches on osty valves. 3/14/00 11:21:42 AM
|