FIR03-00558
| INSP-Final Inspection | 3/9/2004 | 3/10/2004 | 3/10/2004 12:00:00 AM | A | PASS |
|
|
fire sprinklers finaled 3/10/2004 8:28:15 AM
|
BLD03-01197
| FIRE-Final Inspection | 3/9/2004 | 3/10/2004 | 3/10/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 3/10/2004 8:29:07 AM
|
BLD02-03053
| FIRE-Final Inspection | 3/9/2004 | 3/10/2004 | 3/10/2004 12:00:00 AM | A | FAIL |
|
|
Duct smoke detectors have been installed but they do not shut down the hvac units when activated 3/10/2004 9:57:06 AM
|
MIS04-00075
| FIR-Final | 3/9/2004 | 3/10/2004 | 3/10/2004 12:00:00 AM | A | FAIL |
|
|
Provide annual inspection for the fire extinguisher, remove the deadbolts from the doors. Provide sticker at the main exit. Remove the thumbturn from the main exit. 3/10/2004 9:08:00 AM
|
BLD03-00602
| FIRE-Conference | 3/9/2004 | 3/10/2004 | 3/10/2004 12:00:00 AM | A | PASS |
|
|
First floor sprinkler piping ok to cover in the hard lid areas 3/10/2004 11:32:00 AM
|
FIR03-00484
| INSP-Final Inspection | 3/10/2004 | 3/10/2004 | 3/10/2004 12:00:00 AM | A | PASS |
|
|
Fire sprinklers finaled
|
BLD03-00602
| BLD-Conference | 3/9/2004 | 3/10/2004 | 3/10/2004 12:00:00 AM | P | PASS |
|
|
rooms where risers to 2nd and 3rd floor ok to cover 3/10/2004 4:12:29 PM
|
FIR03-00806
| INSP-Sprinkler Rough-in/Hydro | 3/9/2004 | 3/10/2004 | 3/10/2004 12:00:00 AM | P | PART |
|
|
Inspection was for the start of the 24 hour air test. Piping in the attic is at 49psi and the riser is at 46psi 3/10/2004 3:04:56 PM
|
FIR03-00713
| INSP-Final Inspection | 3/9/2004 | 3/10/2004 | 3/10/2004 12:00:00 AM | P | PASS |
|
|
Fire sprinklers finaled 3/10/2004 2:20:31 PM
|