Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00756 FIR-Aging Inspection3/10/20053/10/20053/10/2005 12:00:00 AM NR
Per Mike the system is installed but they are waiting on the tie into the existing fire alarm sytem 3/10/2005 3:44:31 PM
FIR04-00219 INSP-Final Inspection3/8/20053/10/20053/10/2005 12:00:00 AMAFAIL
Need to final both FIR pemits, add exit sign and emergency light in stairwell and repair the exit lights in the tenant space. Test em all when done 3/10/2005 9:59:42 AM
BLD04-02711 FIRE-Final Inspection3/9/20053/10/20053/10/2005 12:00:00 AMAPASS
fire life safety finaled 3/10/2005 9:21:49 AM
BLD04-02975 FIRE-Final Inspection3/9/20053/10/20053/10/2005 12:00:00 AMAPASS
fire life safety finaled 3/10/2005 11:25:41 AM
FIR05-00081 INSP-Final Inspection3/9/20053/10/20053/10/2005 12:00:00 AMAPASS
fire alarm finaled 3/10/2005 11:55:00 AM
BLD05-00012 FIRE-Final Inspection3/9/20053/10/20053/10/2005 12:00:00 AMAFAIL
Delete one exit sign and relocate another in the existing area as discussed and per approved plans 3/10/2005 8:53:10 AM
FIR05-00008 INSP-Final Inspection3/9/20053/10/20053/10/2005 12:00:00 AMAPASS
Fire sprinklers finaled 3/10/2005 1:44:30 PM
BLD04-02824 FIRE-Final Inspection3/9/20053/10/20053/10/2005 12:00:00 AMAFAIL
Provide approved door hardware on both doors. Provide fire extinguisher per review comments. 3/10/2005 12:33:29 PM
BLD04-01073 FIRE-Final Inspection3/9/20053/10/20053/10/2005 12:00:00 AMAPASS
Fire life safety finaled 3/10/2005 1:57:31 PM
FIR04-00186 INSP-Final Inspection3/10/20053/10/20053/10/2005 12:00:00 AMAFAIL
Missing ceiling tile and canopies.
FIR04-00219 INSP-Final Inspection3/10/20053/10/20053/10/2005 12:00:00 AMAFAIL
Instead on one notification circuit there are now two. NAC 2 and NAC 10. Resubmit plans for approval
BLD04-02124 FIRE-Final Inspection3/10/20053/10/20053/10/2005 12:00:00 AMAPASS
Fire life safety finaled
FIR05-00031 INSP-Final Inspection3/10/20053/10/20053/10/2005 12:00:00 AMAPASS
fire sprinkler finaled
FIR05-00063 INSP-Final Inspection3/10/20053/10/20053/10/2005 12:00:00 AMPPART
A temporary occupancy was given with Renn Ross's permission. Fire alarm has been pretested and just needs to be witnessed by the fire inspector.
BLD04-02809 FIRE-Final Inspection3/10/20053/10/20053/10/2005 12:00:00 AMPPART
A temporary occupancy was given with Renn Ross's permission. Fire alarm has been pretested and just needs to be witnessed by the fire inspector. Fire life safety is ok to final when the fire alarm is approved.
FIR04-00689 INSP-Final Inspection3/10/20053/10/20053/10/2005 12:00:00 AMPPASS
Fire sprinkler finaled
BLD04-02887 FIRE-Conference3/10/20053/10/20053/10/2005 12:00:00 AMPDONE
Contractor had questions about the fire rated corridor. 3/10/2005 4:35:47 PM
FIR04-00593 INSP-Sprinkler Rough-in/Hydro3/10/20053/10/20053/10/2005 12:00:00 AMPPASS
Hydro test for the underground passed. Done by Bill Alexander. 3/10/2005 3:42:56 PM
FIR04-00666 INSP-Sprinkler Rough-in/Hydro3/9/20053/10/20053/10/2005 12:00:00 AMPPASS
Hydro test for the wet system, dry system and the underground supply passed. Still need to hydro the header and the fdc. Also need the 24 hour air test on the dry system done. 3/10/2005 3:40:47 PM
BLD04-02124 FIRE-Final Inspection3/10/20053/10/20053/10/2005 12:00:00 AMPPASS
life safety finaled 3/10/2005 11:06:35 AM