Inspections for the day of: Friday, March 10, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03909 ELE-Aging Inspection3/10/20063/10/20063/14/2006 3:13:53 PM FAIL
still needs bld permit talked with carrol of code enforcement they are to folloe up also talked with Tom A, notice was posted
ELE05-02612 Rough-In Permanent Service3/6/20063/10/20063/10/2006 3:11:44 PMPPASS
Jack; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong p/s o/h rec. ok
ELE06-00433 Final3/10/20063/10/20063/10/2006 2:21:48 PMPFAIL
ext 39-- kris; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
406.4(B&D) recepts loose and not set in plate 300.7 shall seal raceways to cooler, freezer inside and outside of raceways,, 210.8(B)(2) all recpts in kit gfci cash wrap recepts corr. posted called
ELE05-04214 Rough-In Permanent Service3/10/20063/10/20063/10/2006 1:33:14 PMPPASS
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/ p/s u/g new ok
ELE05-04213 Rough-In Permanent Service3/10/20063/10/20063/10/2006 1:32:42 PMPPASS
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i p/s u/g new ok
ELE05-04210 Rough-In Permanent Service3/10/20063/10/20063/10/2006 1:32:15 PMPPASS
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/ p/s u/g new ok
ELE05-04209 Rough-In Permanent Service3/10/20063/10/20063/10/2006 1:31:34 PMPPASS
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles r/i p/s u/g new ok
ELE06-00828 Temporary Service3/10/20063/10/20063/10/2006 12:01:02 PMPFAIL
###-#### - rock corr. posted called left message, 250.24(A)(1) shall terminate GEC to terminal or bus that neutral is terminated to
ELE05-04665 Final3/9/20063/10/20063/10/2006 10:23:59 AMANH
charlie Internet Inspection Request from: Melyne Davis no access notice posted called
ELE06-00772 Rough-In Permanent Service3/9/20063/10/20063/10/2006 9:55:57 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: William Zerfas do not cover posted called BLD permit states no duplex or ADU house has a seperate apartment on 1st floor, if allowed p/s needs calculations I think it is too small it's only 200 amp
ELE06-00686 Electrical Rough-In3/9/20063/10/20063/10/2006 9:52:16 AMAFAIL
Rough inspection on detached garage only. House has passed rough already.; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson do not cover posted called left message, needs to update electrical permit for 2 p/s and correct bld permit too show detached shop on permit
ELE06-00718 Rough-In Permanent Service3/10/20063/10/20063/10/2006 8:40:15 AMAPASS
r/i p/s o/h new ok
ELE06-00718 Final3/9/20063/10/20063/10/2006 8:15:16 AMACANC
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange
ELE06-00824 Final3/9/20063/10/20063/10/2006 8:03:54 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok
ELE05-03679 DOC - Permit Finaled3/10/20063/10/20063/10/2006 12:00:00 AMAPASS