Inspections for the day of: Friday, March 10, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01642 ELE-Aging Inspection3/10/20063/10/20063/14/2006 3:12:37 PM DONE
nr
ELE04-00301 ELE-Aging Inspection3/10/20063/10/20063/14/2006 3:12:16 PM DONE
nr
ELE06-00801 Rough-In Permanent Service3/9/20063/10/20063/10/2006 4:17:15 PMPFAIL
Brandon; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong met owner, left corr notice,300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A) (1) receptacles shall be spaced so that no point is over 6' from a recpt horizontally along the floor line,334.30 nm cable shall be stapled within 8" of box, Note, smoke detector will be required in bedroom
ELE05-03886 Final3/10/20063/10/20063/10/2006 4:15:28 PMPPART
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs met contr, left corr notice, did not sign card,330.30(B) mc cable shall be supported within 12" of box,314.27(C) floor box covers shall be listed as part of assembly,348.30(A) flex metal conduit shall be secured within 12" of box,210.62 show room receptacles shall be installed, 358.30 emt shall be secured within 3' of box, 400.8 flexible cords shall not be used as a substitute for fixed wiring, 408.4 circuit directories shall be completed, 110.3(A) only listed equipment shall be installed, 300.4 conductors shall be protected where subject to physical damage
ELE05-03916 Electrical Rough-In3/9/20063/10/20063/10/2006 3:57:54 PMPCANC
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL wrong number, see ele06-00179
ELE06-00113 Electrical Rough-In3/10/20063/10/20063/10/2006 3:09:58 PMPPART
contact: Lyle Dean - Inpection for 6th floor, North end; Phone #: ###-#### Internet Inspection Request from: Deb McCoy walls only anop, 5 rooms
ELE06-00826 Electrical Rough-In3/10/20063/10/20063/10/2006 2:03:52 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to cover u/g
ELE06-00810 Electrical Rough-In3/10/20063/10/20063/10/2006 1:26:33 PMPPASS
Please call Kevin Burke at ###-#### before inspection. Thanks; Phone #: ###-#### Internet Inspection Request from: Jim Williams shop and bath ok to cover
ELE05-00537 Permanent Service3/10/20063/10/20063/10/2006 1:12:14 PMPPASS
Feeder Inspection for Panel; Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s, exst meter pak ,n, ok
ELE06-00819 Permanent Service3/9/20063/10/20063/10/2006 9:44:39 AMACANC
Roy; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, wrong address, he will fix and recall
ELE06-00088 Final3/9/20063/10/20063/10/2006 9:06:44 AMAFAIL
acess code 3174; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called contr, left corr notice, 406.4 receptacles shall be mounted in boxes designed for the purpose and they shall be securely fastened in place.
ELE06-00790 Electrical Rough-In3/9/20063/10/20063/10/2006 9:03:59 AMAPART
Scheduled by a contractor via Hello! on 3/9/2006 at 3:24:37 PM. Contact: ###-####. ok to cover walls anop, nw and column east
ELE06-00822 Temporary Service3/9/20063/10/20063/10/2006 8:41:40 AMAFAIL
Kim; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left corr noice, 312.5 all conductors entering enclosure shall have abrasion protection, 250.24(A) wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected, 408.4 circuit directory shall be provided, 310.7 conductors used for direct burial shall be of a type identified for such use, BCC job id sticker shall be posted
ELE06-00179 Electrical Rough-In3/10/20063/10/20063/10/2006 12:00:00 AMPPASS
ceiling ok to cover mri room