ELE05-01642
| ELE-Aging Inspection | 3/10/2006 | 3/10/2006 | 3/14/2006 3:12:37 PM | | DONE |
|
|
nr
|
ELE04-00301
| ELE-Aging Inspection | 3/10/2006 | 3/10/2006 | 3/14/2006 3:12:16 PM | | DONE |
|
|
nr
|
ELE06-00801
| Rough-In Permanent Service | 3/9/2006 | 3/10/2006 | 3/10/2006 4:17:15 PM | P | FAIL |
|
|
Brandon; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong met owner, left corr notice,300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A) (1) receptacles shall be spaced so that no point is over 6' from a recpt horizontally along the floor line,334.30 nm cable shall be stapled within 8" of box, Note, smoke detector will be required in bedroom
|
ELE05-03886
| Final | 3/10/2006 | 3/10/2006 | 3/10/2006 4:15:28 PM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs met contr, left corr notice, did not sign card,330.30(B) mc cable shall be supported within 12" of box,314.27(C) floor box covers shall be listed as part of assembly,348.30(A) flex metal conduit shall be secured within 12" of box,210.62 show room receptacles shall be installed, 358.30 emt shall be secured within 3' of box, 400.8 flexible cords shall not be used as a substitute for fixed wiring, 408.4 circuit directories shall be completed, 110.3(A) only listed equipment shall be installed, 300.4 conductors shall be protected where subject to physical damage
|
ELE05-03916
| Electrical Rough-In | 3/9/2006 | 3/10/2006 | 3/10/2006 3:57:54 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL wrong number, see ele06-00179
|
ELE06-00113
| Electrical Rough-In | 3/10/2006 | 3/10/2006 | 3/10/2006 3:09:58 PM | P | PART |
|
|
contact: Lyle Dean - Inpection for 6th floor, North end; Phone #: ###-#### Internet Inspection Request from: Deb McCoy walls only anop, 5 rooms
|
ELE06-00826
| Electrical Rough-In | 3/10/2006 | 3/10/2006 | 3/10/2006 2:03:52 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to cover u/g
|
ELE06-00810
| Electrical Rough-In | 3/10/2006 | 3/10/2006 | 3/10/2006 1:26:33 PM | P | PASS |
|
|
Please call Kevin Burke at ###-#### before inspection. Thanks; Phone #: ###-#### Internet Inspection Request from: Jim Williams shop and bath ok to cover
|
ELE05-00537
| Permanent Service | 3/10/2006 | 3/10/2006 | 3/10/2006 1:12:14 PM | P | PASS |
|
|
Feeder Inspection for Panel; Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s, exst meter pak ,n, ok
|
ELE06-00819
| Permanent Service | 3/9/2006 | 3/10/2006 | 3/10/2006 9:44:39 AM | A | CANC |
|
|
Roy; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, wrong address, he will fix and recall
|
ELE06-00088
| Final | 3/9/2006 | 3/10/2006 | 3/10/2006 9:06:44 AM | A | FAIL |
|
|
acess code 3174; Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS called contr, left corr notice, 406.4 receptacles shall be mounted in boxes designed for the purpose and they shall be securely fastened in place.
|
ELE06-00790
| Electrical Rough-In | 3/9/2006 | 3/10/2006 | 3/10/2006 9:03:59 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 3/9/2006 at 3:24:37 PM. Contact: ###-####. ok to cover walls anop, nw and column east
|
ELE06-00822
| Temporary Service | 3/9/2006 | 3/10/2006 | 3/10/2006 8:41:40 AM | A | FAIL |
|
|
Kim; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong called contr, left corr noice, 312.5 all conductors entering enclosure shall have abrasion protection, 250.24(A) wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected, 408.4 circuit directory shall be provided, 310.7 conductors used for direct burial shall be of a type identified for such use, BCC job id sticker shall be posted
|
ELE06-00179
| Electrical Rough-In | 3/10/2006 | 3/10/2006 | 3/10/2006 12:00:00 AM | P | PASS |
|
|
ceiling ok to cover mri room
|