Inspections for the day of: Monday, March 10, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00888 INSP-Final Inspection3/7/20083/10/20083/11/2008 5:00:02 PMAFAIL
PIV tamper switch is out of adjustment, smoke alarms at some locations do not meet NFPA 72 2002 11.8.3.5 (5), one minor programming issue corrected while on site.
FIR07-00235 INSP-Final Inspection3/10/20083/10/20083/11/2008 4:55:09 PMPFAIL
PIV tamper switch is out of adjustment, missing orfice at inspectors test, noted leakage at the riser to be repaired, need signage at the risers indicating location of system served, missing "911" sign at the bell, permit work is not complete for final at this time.
FIR07-00236 INSP-Final Inspection3/10/20083/10/20083/11/2008 4:50:44 PMPFAIL
Missing some required finish items including FDC cap, "911" sign at the bell, breakaway lock at the PIV, restricted inspectors test, some items at the riser, also missing one system flow switch due to be replaced, project is not in condition for final at this time.
FIR07-00482 INSP-Final Inspection3/10/20083/10/20083/11/2008 4:46:11 PMAPASS
Fire sprinkler permit finaled.
BLD06-00077 FIRE-Final Inspection3/10/20083/10/20083/11/2008 4:43:28 PMPNR
Pending sprinkler and alarm finals.
BLD06-00076 FIRE-Final Inspection3/10/20083/10/20083/11/2008 4:42:52 PMPNR
Need project related fire alarm and sprinkler permit finals prior to building fire life safety approval.
BLD06-00075 FIRE-Final Inspection3/10/20083/10/20083/11/2008 4:41:47 PMPNR
Final pending completed fire alarm and fire sprinkler permit work.
BLD07-02335 FIRE-Final Inspection3/7/20083/10/20083/10/2008 11:09:05 AMAPASS
Fire life safety final inspection passed, agreed to allow posting of temporary max occupant load signs with verification by receipt that permanent signs have been ordered, items on correction notice are finished, verified with plan reviewer R. Hill relocation of the front street exit door to 12th street is acceptable.