FIR10-00579
| INSP-Sprinkler Rough-in | 3/10/2011 | 3/10/2011 | 3/10/2011 3:19:45 PM | P | PASS |
|
|
Remaining sprinkler rough-in passed. Noted additional fittings affecting remote areas 2 and 3 but per Tim the hydraulic calculations are adequate. I also noted side wall heads under overhead doors that were not shown on the plans. One door at the east end of the service bay is going to be provided with an extended coverage sidewall that will need to be field approved. I also noted that the existing pendant sprinklers in the sales area are being blocked by suspended light fixtures. This problem will need to be addressed prior to final sign off. It appears that if the lights are mounted to the ceiling they will no longer be an obstruction.
|
FIR10-00510
| INSP-Sprinkler Rough-in | 3/10/2011 | 3/10/2011 | 3/10/2011 3:18:14 PM | P | PASS |
|
|
Remaining sprinkler rough-in passed. Noted additional fittings affecting remote areas 2 and 3 but per Tim the hydraulic calculations are adequate. I also noted side wall heads under overhead doors that were not shown on the plans. One door at the east end of the service bay is going to be provided with an extended coverage sidewall that will need to be field approved. I also noted that the existing pendant sprinklers in the sales area are being blocked by suspended light fixtures. This problem will need to be addressed prior to final sign off. It appears that if the lights are mounted to the ceiling they will no longer be an obstruction.
|
FIR11-00019
| INSP-Sprinkler Rough-in | 3/10/2011 | 3/10/2011 | 3/10/2011 2:55:46 PM | P | PASS |
|
|
Sprinkler piping can be covered. The light in the restroom needs to be rotated away from the sprinkler pendant to avoid being an obstruction.
|
BLD10-00031
| FIRE-Final Inspection | 3/9/2011 | 3/10/2011 | 3/10/2011 1:25:07 PM | A | PASS |
|
|
life safety passed
|
BLD09-02285
| FIRE-Conference | 3/9/2011 | 3/10/2011 | 3/10/2011 10:22:29 AM | A | FAIL |
|
|
Provide a 2A10BC fire extinguisher in a normal path of travel as discussed and provide single action hardware on all doors as per the approved plans. Also remove the thumbturn lock on the main exit. Keyed is ok with the "indicator".
|