Inspections for the day of: Thursday, March 10, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00579 INSP-Sprinkler Rough-in3/10/20113/10/20113/10/2011 3:19:45 PMPPASS
Remaining sprinkler rough-in passed. Noted additional fittings affecting remote areas 2 and 3 but per Tim the hydraulic calculations are adequate. I also noted side wall heads under overhead doors that were not shown on the plans. One door at the east end of the service bay is going to be provided with an extended coverage sidewall that will need to be field approved. I also noted that the existing pendant sprinklers in the sales area are being blocked by suspended light fixtures. This problem will need to be addressed prior to final sign off. It appears that if the lights are mounted to the ceiling they will no longer be an obstruction.
FIR10-00510 INSP-Sprinkler Rough-in3/10/20113/10/20113/10/2011 3:18:14 PMPPASS
Remaining sprinkler rough-in passed. Noted additional fittings affecting remote areas 2 and 3 but per Tim the hydraulic calculations are adequate. I also noted side wall heads under overhead doors that were not shown on the plans. One door at the east end of the service bay is going to be provided with an extended coverage sidewall that will need to be field approved. I also noted that the existing pendant sprinklers in the sales area are being blocked by suspended light fixtures. This problem will need to be addressed prior to final sign off. It appears that if the lights are mounted to the ceiling they will no longer be an obstruction.
FIR11-00019 INSP-Sprinkler Rough-in3/10/20113/10/20113/10/2011 2:55:46 PMPPASS
Sprinkler piping can be covered. The light in the restroom needs to be rotated away from the sprinkler pendant to avoid being an obstruction.
BLD10-00031 FIRE-Final Inspection3/9/20113/10/20113/10/2011 1:25:07 PMAPASS
life safety passed
BLD09-02285 FIRE-Conference3/9/20113/10/20113/10/2011 10:22:29 AMAFAIL
Provide a 2A10BC fire extinguisher in a normal path of travel as discussed and provide single action hardware on all doors as per the approved plans. Also remove the thumbturn lock on the main exit. Keyed is ok with the "indicator".