FIR12-00717
| INSP-Sprinkler Rough-in/Hydro | 3/10/2014 | 3/10/2014 | 3/11/2014 2:10:43 PM | P | PART |
|
|
phase 3 main and branchline rough-in passed. Will still need rough-in inspection for the drops
|
FIR14-00109
| INSP-Sprinkler Rough-in | 3/10/2014 | 3/10/2014 | 3/10/2014 3:05:30 PM | P | PASS |
|
|
See the city approved plans for locations where the piping can be covered.
|
FIR14-00120
| INSP-Final Inspection | 3/7/2014 | 3/10/2014 | 3/10/2014 12:06:59 PM | A | PASS |
|
|
permit finaled
|
FIR13-00633
| INSP-Alarm Testing | 3/6/2014 | 3/10/2014 | 3/10/2014 10:20:00 AM | A | PART |
|
|
See the city approved plans for locations of the smoke detectors tested. They are marked "ok" in red. I also tested/verified the audio/visual devices in this same area. The devices that did not function were the fire/smoke dampers.
|
FIR13-00701
| INSP-Final Inspection | 3/10/2014 | 3/10/2014 | 3/10/2014 10:16:43 AM | P | PASS |
|
|
permit finaled
|
BLD13-02770
| FIRE-Final Inspection | 3/10/2014 | 3/10/2014 | 3/10/2014 10:15:55 AM | P | PASS |
|
|
life safety passed
|
FIR13-00701
| INSP-Alarm Testing | 3/6/2014 | 3/10/2014 | 3/10/2014 10:14:01 AM | A | PASS |
|
|
Permit finaled. Two new strobes added as requested.
|