BLD14-03632
| FIRE-Conference | 3/10/2015 | 3/10/2015 | 3/11/2015 2:17:21 PM | P | DONE |
|
|
David and I went over life safety requirements. I noted that an address needs to be posted at the top of the hill/property entrance and door hardware provided. Plan review comments have been modified to show the fuel pump
|
NAF14-00004
| INSP-Final | 3/9/2015 | 3/10/2015 | 3/10/2015 3:23:17 PM | P | PASS |
|
|
Permit finaled. Manual pull station was lowered while I waited and then tested. No baking/drying process per Owner and installing contractor. Three nozzles in paint area, one in exhuast and one behind the filters.
|
FIR14-00617
| INSP-Sprinkler Rough-in | 3/10/2015 | 3/10/2015 | 3/10/2015 3:19:54 PM | P | FAIL |
|
|
Pipe sizing as installed does not match the approved plans. Also no tenting of the sprinkler piping has been performed. No piping to be covered.
|
FIR15-00063
| INSP-Sprinkler Rough-in | 3/10/2015 | 3/10/2015 | 3/10/2015 3:16:24 PM | P | CANC |
|
|
Requested UG cover inspection already approved by inspector 410 on 2/25/2015.
|
FIR14-00867
| INSP-Sprinkler Rough-in/Hydro | 3/10/2015 | 3/10/2015 | 3/10/2015 3:13:47 PM | P | CANC |
|
|
Could not make it for a hydro test. Don is going to reschedule
|
FIR15-00083
| INSP-Final Inspection | 3/4/2015 | 3/10/2015 | 3/10/2015 3:11:13 PM | P | CANC |
|
|
Rescheduled for thurday morning
|
BLD14-02972
| FIRE-Final Inspection | 3/10/2015 | 3/10/2015 | 3/10/2015 3:09:16 PM | A | FAIL |
|
|
Inspection was for a confernece to discuss the location of duct smoke detectors at the new hvac unit. I quoted IMC code and defered any changes to the mechanical inspector.
|
BLD14-03469
| FIRE-Final Inspection | 3/10/2015 | 3/10/2015 | 3/10/2015 2:07:45 PM | P | PASS |
|
|
life safety passed
|
BLD15-00167
| FIRE-Final Inspection | 3/4/2015 | 3/10/2015 | 3/10/2015 10:39:26 AM | A | FAIL |
|
|
Provide correct suite number and provide the correct size fire extinguisher with current inspection tag
|
BLD14-03645
| FIRE-Final Inspection | 3/10/2015 | 3/10/2015 | 3/10/2015 10:38:51 AM | A | FAIL |
|
|
There were no city approved plans or small documents on site. No inspection performed
|