Inspections for the day of: Thursday, March 10, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-00378 FIRE-Final Inspection3/10/20163/10/20163/10/2016 2:40:24 PMPFAIL
Provide building address on the street side of the building, remove arrow on exit sign directing people to locked door, provide fire dept access signage per notes.
BLD15-00377 FIRE-Final Inspection3/10/20163/10/20163/10/2016 2:39:47 PMPFAIL
Provide building address on the street side of the building, remove arrow on exit sign directing people to locked door, provide fire dept access signage per notes.
FIR16-00055 INSP-Final Inspection3/4/20163/10/20163/10/2016 2:04:14 PMPPASS
Permit finaled
FIR15-00905 INSP-Sprinkler Rough-in/Hydro3/10/20163/10/20163/10/2016 1:59:55 PMPPASS
Rough to cover inspection for underground piping passed. It was agreed that an additional 6" of cover above the level of the adjacent sidewalk will be provided to meet the 4'6" minimum bury depth.