Inspections for the day of: Thursday, March 10, 2016.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00748 INSP-Sprinkler Rough-in3/9/20163/10/20163/10/2016 2:58:53 PMPPART
Tenting inspection complete for the west side of the fire doors located on the third level. Overhead fire sprinkler piping on west side of 3rd level fire doors approved for cover, east side still needs tenting insulation installed and inspection performed. Third level, east side of fire doors cannot be covered until inspection of tenting is completed.
FIR16-00156 INSP-Sprinkler Rough-in3/10/20163/10/20163/10/2016 1:58:43 PMPPASS
Rough to cover inspection complete, area of work approved for cover.
FIR16-00149 INSP-Sprinkler Rough-in3/9/20163/10/20163/10/2016 1:55:26 PMPPASS
Rough to cover inspection complete for the overhead fire sprinkler piping, area of work approved for cover.
FIR16-00028 INSP-Sprinkler Rough-in/Hydro3/10/20163/10/20163/10/2016 1:31:47 PMPFAIL
Underground hydrostatic test failed, contractor had glued plastic fitting come apart during test. Contractor will reschedule inspection after repair is made.
FIR16-00017 INSP-Sprinkler Rough-in/Hydro3/10/20163/10/20163/10/2016 1:28:44 PMPPASS
Underground rough to cover inspection complete, underground supply approved for cover. Hydrostatic test (200psi for 2 hours)for underground passed/complete.
FIR16-00049 INSP-Sprinkler Rough-in/Hydro3/10/20163/10/20163/10/2016 1:27:28 PMAPASS
Underground rough to cover inspection complete, underground supply approved for cover. Hydrostatic test (200psi for 2 hours)for underground passed/complete.
FIR15-00912 INSP-Sprinkler Rough-in3/7/20163/10/20163/10/2016 11:10:47 AMADONE
Fire pump flow/testing complete
FIR16-00012 INSP-Final Inspection3/10/20163/10/20163/10/2016 10:04:11 AMPPASS
Final fire alarm inspection passed/complete
FIR16-00011 INSP-Final Inspection3/9/20163/10/20163/10/2016 10:03:18 AMAPASS
Final fire alarm inspection passed/complete