FIR15-00748
| INSP-Sprinkler Rough-in | 3/9/2016 | 3/10/2016 | 3/10/2016 2:58:53 PM | P | PART |
|
|
Tenting inspection complete for the west side of the fire doors located on the third level. Overhead fire sprinkler piping on west side of 3rd level fire doors approved for cover, east side still needs tenting insulation installed and inspection performed. Third level, east side of fire doors cannot be covered until inspection of tenting is completed.
|
FIR16-00156
| INSP-Sprinkler Rough-in | 3/10/2016 | 3/10/2016 | 3/10/2016 1:58:43 PM | P | PASS |
|
|
Rough to cover inspection complete, area of work approved for cover.
|
FIR16-00149
| INSP-Sprinkler Rough-in | 3/9/2016 | 3/10/2016 | 3/10/2016 1:55:26 PM | P | PASS |
|
|
Rough to cover inspection complete for the overhead fire sprinkler piping, area of work approved for cover.
|
FIR16-00028
| INSP-Sprinkler Rough-in/Hydro | 3/10/2016 | 3/10/2016 | 3/10/2016 1:31:47 PM | P | FAIL |
|
|
Underground hydrostatic test failed, contractor had glued plastic fitting come apart during test. Contractor will reschedule inspection after repair is made.
|
FIR16-00017
| INSP-Sprinkler Rough-in/Hydro | 3/10/2016 | 3/10/2016 | 3/10/2016 1:28:44 PM | P | PASS |
|
|
Underground rough to cover inspection complete, underground supply approved for cover. Hydrostatic test (200psi for 2 hours)for underground passed/complete.
|
FIR16-00049
| INSP-Sprinkler Rough-in/Hydro | 3/10/2016 | 3/10/2016 | 3/10/2016 1:27:28 PM | A | PASS |
|
|
Underground rough to cover inspection complete, underground supply approved for cover. Hydrostatic test (200psi for 2 hours)for underground passed/complete.
|
FIR15-00912
| INSP-Sprinkler Rough-in | 3/7/2016 | 3/10/2016 | 3/10/2016 11:10:47 AM | A | DONE |
|
|
Fire pump flow/testing complete
|
FIR16-00012
| INSP-Final Inspection | 3/10/2016 | 3/10/2016 | 3/10/2016 10:04:11 AM | P | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR16-00011
| INSP-Final Inspection | 3/9/2016 | 3/10/2016 | 3/10/2016 10:03:18 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|