Inspections for the day of: Friday, March 10, 2017.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorChad Schwendiman
TitleMEC-INSPECTOR
Phone #780-9549
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC16-03056 Rough-in3/10/20173/10/20173/10/2017 4:14:30 PMPPART
rough in condo 207 Phone #: ###-#### Inspection requested via web by Crystal Grant - unit 207 okay to cover
MEC16-02172 Mec-Aging Inspection3/10/20173/10/20173/10/2017 3:43:27 PM CANC
MEC16-05733 Pressure Test3/10/20173/10/20173/10/2017 3:38:22 PMPPART
Randall Phone #: ###-####-late pm if possible - 60lb gas pass on under ground piping from meter to pool equipment room.
MEC17-00428 Rough-in3/10/20173/10/20173/10/2017 3:37:13 PMPPART
Call Mark for access rough in building 9 Phone #: ###-#### Inspection requested via web by David Tully - okay to cover guest rooms in bldg 9
MEC17-00877 Final3/10/20173/10/20173/10/2017 3:37:12 PMPPASS
Phone #: ###-#### Inspection requested via web by Justin Osterhout
MEC17-00869 Pressure Test3/10/20173/10/20173/10/2017 2:18:45 PMPPASS
Call 1hr please - Brandon Phone #: ###-#### - 20lb gas
MEC17-00869 Final3/10/20173/10/20173/10/2017 2:17:48 PMPPASS
Call 1hr please - Brandon Phone #: ###-####
MEC17-00729 Final3/8/20173/10/20173/10/2017 2:03:33 PMPPASS
Homeowner, Lilly Vojvodic ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
MEC16-03546 Mec-Aging Inspection3/10/20173/10/20173/10/2017 12:04:16 PM CANC
wip
MEC17-00806 Final3/8/20173/10/20173/10/2017 12:02:53 PMAFAIL
Angie-would like as late am as possible Phone #: ###-####-please call to meet - This should have been a rough in. need to submitt a manual J for approval, Need 1" clearance to combustables from b-vent, need 6" clearance to combustables from single wall vent, need to vent bath fan. Need to get plumbing permit
MEC17-00181 Final3/7/20173/10/20173/10/2017 11:35:02 AMAPASS
Homeowner not present, Workers supposed to be there all week. Phone #: ###-#### Inspection requested via web by Mary LaFayette
MEC16-02661 Rough-in3/9/20173/10/20173/10/2017 10:50:34 AMAPART
Call Cary for access. Cover for conference room 3rd floor and cover for 6th floor rooms east side. Phone #: ###-#### Inspection requested via web by David Tully - okay to cover guest rooms on the east side of the 6th floor. framing around fire/smoke danpers okay for 3rd floor conference room
MEC16-03552 Mec-Aging Inspection3/10/20173/10/20173/10/2017 9:46:12 AM PASS
MEC16-03552 DOC - Permit Finaled3/10/20173/10/20173/10/2017 9:46:00 AMAPASS
MEC16-05733 Pressure Test3/9/20173/10/20173/10/2017 9:31:50 AMAPART
randall Phone #: ###-#### - 20lb gas pass to fireplace in office bldg. met and looked at underground gas piping to pool heatetrs, bbq, and fire pit. the existing piping is undersized and needs to be brought up to current codes. I spoke with Randall about increasing the gas pressure to a 2lb system with regulators to avoid having to repipe the whole system.
MEC17-00797 Rough-in3/9/20173/10/20173/10/2017 9:15:06 AMAPASS
Phone #: ###-#### Inspection requested via web by Troy Worley