FIR19-00540
| INSP-Sprinkler Rough-in/Hydro | 3/10/2020 | 3/10/2020 | 3/10/2020 2:36:39 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauges.
Robert Chambers is the contact. Thanks! Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00551
| INSP-Sprinkler Rough-in/Hydro | 3/10/2020 | 3/10/2020 | 3/10/2020 2:36:23 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauges.
Robert Chambers is the contact. Thanks! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00393
| FIRE-Final Inspection | 3/10/2020 | 3/10/2020 | 3/10/2020 12:38:22 PM | P | PASS |
|
|
Previously noted items have been corrected, final life fire safety inspection for scope of work is complete, signature card not available at time of inspection.
Fire Safety Inspection Phone #: ###-#### Inspection requested via web by John Boyd
|
FIR19-00809
| INSP-Final Inspection | 3/10/2020 | 3/10/2020 | 3/10/2020 11:00:59 AM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Thank you Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR20-00095
| INSP-Final Inspection | 3/9/2020 | 3/10/2020 | 3/10/2020 10:40:43 AM | P | PASS |
|
|
Final inspection for scope of work has been completed, complete fire alarm system has been removed.
Anthony Phone #: ###-####
|
BLD19-03779
| FIRE-Final Inspection | 3/9/2020 | 3/10/2020 | 3/10/2020 10:11:49 AM | A | FAIL |
|
|
Fire sprinkler modifications are required in area of work, fire sprinkler modifications will reuqire a seperate permit. Entry door hardware does not comply with 1010.1.9.1 of the 2015 International Fire Code. Provide annual inspection on fire extinguishers and wall mount fire extinguishers as discussed, extinguishers are not to be placed on the floor per code requirements, extinguisher must be mounted, not less than 4 inches off of the floor and not more than 48 inches to extinguisher mechanism.
Paul- please call for access Phone #: ###-####
|
FIR19-00551
| INSP-Sprinkler Rough-in/Hydro | 3/6/2020 | 3/10/2020 | 3/10/2020 9:22:39 AM | A | CANC |
|
|
Rescheduled for PM, this request is cancelled.
Robert Chambers is the contact. Thanks! (: Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00540
| INSP-Sprinkler Rough-in/Hydro | 3/6/2020 | 3/10/2020 | 3/10/2020 9:22:04 AM | A | CANC |
|
|
Robert Chambers is the contact. Thanks! (: Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-04631
| FIRE-Final Inspection | 3/9/2020 | 3/10/2020 | 3/10/2020 8:40:28 AM | A | PASS |
|
|
No fire sprinkler modifications, fire alarm inspection is complete, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.
call 20 minutes ahead // Garrett Phone #: ###-####
|