Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-00409 Electrical Rough-In3/11/20033/11/20033/11/2003 8:18:20 AMPCANC
Exterior can lights.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs Inspection cancelled from web by: Kathy Briggs
ELE03-00628 Rough-In Permanent Service3/4/20033/11/20033/11/2003 12:00:00 AMAFAIL
STEVE; Phone #: ###-#### Internet Inspection Request from: Darla Downs cor. posted called 300.4 nail plates and 11/4 for all cables 110.14(A) loose screws bond bushing 3/11/2003 10:43:08 AM
ELE02-03003 Final3/10/20033/11/20033/11/2003 12:00:00 AMAFAIL
CHRIS; Phone #: ###-#### Internet Inspection Request from: Darla Downs corrections gfci wiring or device messed up called 3/11/2003 10:19:58 AM
ELE03-00110 Final3/10/20033/11/20033/11/2003 12:00:00 AMAPASS
steve; Phone #: ###-#### Internet Inspection Request from: Annette Moore ok 3/11/2003 9:16:06 AM
ELE03-00347 Conference3/10/20033/11/20033/11/2003 12:00:00 AMAPART
###-#### conference ok 3/11/2003 11:20:39 AM
ELE03-00709 Electrical Rough-In3/10/20033/11/20033/11/2003 12:00:00 AMAFAIL
joe; Phone #: ###-#### Internet Inspection Request from: Darla Downs notice posted not ready called 3/11/2003 8:49:45 AM
ELE03-00459 Final3/10/20033/11/20033/11/2003 12:00:00 AMAPASS
###-#### ok 3/11/2003 9:55:11 AM
ELE02-03965 Electrical Rough-In3/11/20033/11/20033/11/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 3/11/2003 at 7:28:32 AM. Contact: ###-####. ceilings east side of corridor 3/11/2003 1:33:08 PM
ELE03-00728 Rough-In Permanent Service3/11/20033/11/20033/11/2003 12:00:00 AMAPASS
r/i ok


p/s u/g new ok 3/11/2003 5:02:09 PM
ELE03-00521 Rough-In Permanent Service3/11/20033/11/20033/11/2003 12:00:00 AMPPASS
bob; Phone #: ###-#### Internet Inspection Request from: Annette Moore shall not ID 6 or smaller grd to sub panel called u/g ok r/i
p/s u/g new ok 3/11/2003 4:37:59 PM
ELE03-00409 Electrical Rough-In3/11/20033/11/20033/11/2003 12:00:00 AMPPART
Exterior can lights; inside ceiling for cover.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok low voltage needs bushings , no cords above ceiling security cameras 3/11/2003 3:49:24 PM
ELE03-00722 Final3/11/20033/11/20033/11/2003 12:00:00 AMPPASS
###-#### ok 3/11/2003 2:41:18 PM
ELE02-03679 Final3/11/20033/11/20033/11/2003 12:00:00 AMPFAIL
CHJRIS ; Phone #: ###-#### Internet Inspection Request from: Annette Moore clearence panel move fence 110.26 (F)(2) 3/11/2003 12:02:56 PM
ELE02-02740 Final3/11/20033/11/20033/11/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 3/11/2003 at 9:32:52 AM. Contact: ###-####. ok 3/11/2003 4:12:33 PM
ELE03-00102 Final3/11/20033/11/20033/11/2003 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 3/11/2003 at 9:42:55 AM. Contact: ###-####. cor. posted called 210.8 (B) gfci for all food prep areas, 110.2,3, U A C 107 tests, eguip in sushi bar area shall be labeled and listed could not find it counter top refer units, all from Japan 3/11/2003 3:24:45 PM
ELE03-00361 Final3/11/20033/11/20033/11/2003 12:00:00 AMPPASS
sign for Imports Parts; Phone #: ###-#### Internet Inspection Request from: Susie Seltzer ok 3/11/2003 3:47:52 PM
ELE03-00391 Final3/11/20033/11/20033/11/2003 12:00:00 AMPPASS
sign for Fujiyama; Phone #: ###-#### Internet Inspection Request from: Susie Seltzer ok 3/11/2003 3:25:03 PM
ELE03-00313 Final3/11/20033/11/20033/11/2003 12:00:00 AMPPASS
DARYL; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok 3/11/2003 2:14:28 PM