BLD02-02753
| FIRE-Final Inspection | 3/10/2004 | 3/11/2004 | 3/11/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 3/11/2004 11:30:47 AM
|
BLD03-00654
| FIRE-Final Inspection | 3/10/2004 | 3/11/2004 | 3/11/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 3/11/2004 9:41:48 AM
|
BLD03-03068
| FIRE-Final Inspection | 3/10/2004 | 3/11/2004 | 3/11/2004 12:00:00 AM | A | CANC |
|
|
MARK; Phone #: ###-#### Internet Inspection Request from: Darla Downs mark called to canc this inspection not ready///dld
|
FIR04-00060
| INSP-Sprinkler Rough-in/Hydro | 3/10/2004 | 3/11/2004 | 3/11/2004 12:00:00 AM | A | FAIL |
|
|
Extended coverage pendants have been installed in locations shown for standard coverage pendants. Provide correct pendant or approval from Bill Alexander for change of installation. Provide additional hangers on all arm overs exceeding 24" in length per NFPA 13 9.2.3.5.1. Provide final for the shell system. This inspection was for rough-in only. 3/11/2004 10:45:29 AM
|
FIR03-00480
| INSP-Final Inspection | 3/9/2004 | 3/11/2004 | 3/11/2004 12:00:00 AM | A | FAIL |
|
|
Fire sprinkler system is ready to final when the alarms have been tested 3/11/2004 9:31:44 AM
|
MIS04-00047
| FIR-Final | 3/9/2004 | 3/11/2004 | 3/11/2004 12:00:00 AM | A | PASS |
|
|
fire life safety finaled 3/11/2004 11:02:39 AM
|
FIR03-00806
| INSP-Sprinkler Rough-in/Hydro | 3/10/2004 | 3/11/2004 | 3/11/2004 12:00:00 AM | P | PART |
|
|
24 hour air test is ok 3/11/2004 4:30:25 PM
|
FIR03-00214
| INSP-Supply line flush | 3/11/2004 | 3/11/2004 | 3/11/2004 12:00:00 AM | P | CANC |
|
|
United water could not find the water valve to turn on underground water supply 3/11/2004 3:36:47 PM
|
BLD03-02027
| FIRE-Final Inspection | 3/11/2004 | 3/11/2004 | 3/11/2004 12:00:00 AM | P | FAIL |
|
|
Provide approved door hardware on all of the interior doors. 3/11/2004 2:25:09 PM
|
MIS04-00074
| FIR-Final | 3/11/2004 | 3/11/2004 | 3/11/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 3/11/2004 1:01:29 PM
|