BLD05-02158
| FIRE-Final Inspection | 3/11/2008 | 3/11/2008 | 3/11/2008 5:12:45 PM | A | NR |
|
|
Pending fire alarm work.
|
FIR06-00889
| INSP-Final Inspection | 3/10/2008 | 3/11/2008 | 3/11/2008 5:05:03 PM | A | NR |
|
|
Missing waterflow switch at one riser, smoke alarms at some locations do not comply with NFPA 72 2002 11.8.3.5 (5).
|
BLD07-02548
| FIRE-Final Inspection | 3/10/2008 | 3/11/2008 | 3/11/2008 4:40:41 PM | A | PASS |
|
|
Fire life safety finaled.
|
FIR07-00606
| INSP-Sprinkler Rough-in | 3/10/2008 | 3/11/2008 | 3/11/2008 4:39:52 PM | P | PART |
|
|
Field inspection completed for the 2nd floor media center area seismic attatchments for beam clamps at hanger rods.
|
BLD07-02586
| FIRE-Final Inspection | 3/10/2008 | 3/11/2008 | 3/11/2008 4:37:21 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
FIR08-00029
| INSP-Final Inspection | 3/11/2008 | 3/11/2008 | 3/11/2008 4:36:39 PM | P | PASS |
|
|
Noted corrections have been completed, fire sprinkler final inspection passed, permit finaled.
|