Inspections for the day of: Wednesday, March 11, 2009.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00065 INSP-Sprinkler Rough-in/Hydro3/11/20093/11/20093/11/2009 3:46:04 PMPFAIL
Sprinkler coverage is lacking in one area as shown on the approved plans. Also there are atleast three locations where new/relocated pendants are piped from the same 1" outlet which is not allowed as per review comment #5. Verify that the existing sprinkler system is current with its annual inspection.
FIR09-00131 INSP-Final Inspection3/11/20093/11/20093/11/2009 3:27:11 PMPCANC
Per the mechanical contractor the damper motors are burned out and will need replaced. The inspection will be called in for next week.
FIR08-00864 INSP-Sprinkler Rough-in/Hydro3/10/20093/11/20093/11/2009 2:43:54 PMPPASS
Permit finaled
FIR09-00153 INSP-Final Inspection3/10/20093/11/20093/11/2009 12:15:45 PMAPASS
permit finaled
FIR08-00864 INSP-Final Inspection3/10/20093/11/20093/11/2009 11:20:46 AMAPASS
The overhead hydro test passed.
FIR09-00131 INSP-Final Inspection3/10/20093/11/20093/11/2009 9:40:51 AMAFAIL
The existing fire/smoke dampers did not function. They are currently in the closed state and appear to be stuck. All other items passed.