FIR09-00065
| INSP-Sprinkler Rough-in/Hydro | 3/11/2009 | 3/11/2009 | 3/11/2009 3:46:04 PM | P | FAIL |
|
|
Sprinkler coverage is lacking in one area as shown on the approved plans. Also there are atleast three locations where new/relocated pendants are piped from the same 1" outlet which is not allowed as per review comment #5. Verify that the existing sprinkler system is current with its annual inspection.
|
FIR09-00131
| INSP-Final Inspection | 3/11/2009 | 3/11/2009 | 3/11/2009 3:27:11 PM | P | CANC |
|
|
Per the mechanical contractor the damper motors are burned out and will need replaced. The inspection will be called in for next week.
|
FIR08-00864
| INSP-Sprinkler Rough-in/Hydro | 3/10/2009 | 3/11/2009 | 3/11/2009 2:43:54 PM | P | PASS |
|
|
Permit finaled
|
FIR09-00153
| INSP-Final Inspection | 3/10/2009 | 3/11/2009 | 3/11/2009 12:15:45 PM | A | PASS |
|
|
permit finaled
|
FIR08-00864
| INSP-Final Inspection | 3/10/2009 | 3/11/2009 | 3/11/2009 11:20:46 AM | A | PASS |
|
|
The overhead hydro test passed.
|
FIR09-00131
| INSP-Final Inspection | 3/10/2009 | 3/11/2009 | 3/11/2009 9:40:51 AM | A | FAIL |
|
|
The existing fire/smoke dampers did not function. They are currently in the closed state and appear to be stuck. All other items passed.
|