BLD11-00405
| FIRE-Final Inspection | 3/11/2011 | 3/11/2011 | 3/11/2011 3:25:07 PM | P | PASS |
|
|
life safety passed
|
FIR11-00077
| INSP-Sprinkler Rough-in | 3/10/2011 | 3/11/2011 | 3/11/2011 3:14:16 PM | A | PASS |
|
|
The remainig sprinkler piping can be covered except as clouded in red on the drawings.
|
BLD11-00429
| FIRE-Final Inspection | 3/11/2011 | 3/11/2011 | 3/11/2011 2:23:43 PM | P | PASS |
|
|
life safety passed.
|
BLD11-00368
| FIRE-Final Inspection | 3/10/2011 | 3/11/2011 | 3/11/2011 2:10:13 PM | A | PASS |
|
|
Life safety passed.
|
BLD11-00090
| FIRE-Final Inspection | 3/11/2011 | 3/11/2011 | 3/11/2011 1:53:09 PM | P | FAIL |
|
|
Provide emergency lighting in both rear exit corridors and in the warehouse. Relocate the fire extinguisher as discussed. Provide building address. Remove the deadbolt/bar on the double rear exit doors.
|
BLD11-00371
| FIRE-Final Inspection | 3/10/2011 | 3/11/2011 | 3/11/2011 11:11:08 AM | A | FAIL |
|
|
Provide 2A10BC fire extinguishers. One for the office area and atleast two for the warehouse area. Provide with current inspection tag at 48"AFF. Contact Carl Madsen to verify if resubmital is required for additional wall and use change in Trash Area. Provide all marked exit signs with emergency lights as discussed. Repair ermergency light in Corridor 111. PRovide sticker at the main exit. Remove the two fire alarm devices.
|
BLD11-00405
| FIRE-Final Inspection | 3/10/2011 | 3/11/2011 | 3/11/2011 10:26:04 AM | A | FAIL |
|
|
Provide single action hardware on the east most exterior exit door and remove the keyed dead bolt. Provide the additional exit sign and relocate the existing sign as discussed.
|