ELE15-00620
| Electrical Rough-In | 3/6/2015 | 3/11/2015 | 3/11/2015 2:43:14 PM | P | PASS |
|
|
homeowner Mike ###-#### Phone #: ###-#### Inspection requested via web by Andy Derrick Ceiling open. Rough in ok cover.
|
ELE15-00650
| Permanent Service | 3/11/2015 | 3/11/2015 | 3/11/2015 2:42:49 PM | P | PASS |
|
|
p/s u/g rec ok
|
ELE15-00620
| Final | 3/11/2015 | 3/11/2015 | 3/11/2015 2:16:32 PM | P | PASS |
|
|
homeowner Mike ###-#### Phone #: ###-#### Inspection requested via web by Andy Derrick Final ok
|
ELE15-00618
| Electrical Rough-In | 3/6/2015 | 3/11/2015 | 3/11/2015 1:51:54 PM | P | FAIL |
|
|
Please call ahead for access - Gary Phone #: ###-#### 210.52- Bathroom receptacle outlet shall be on a 20 amp dedicated circuit.
|
ELE15-00618
| Conference | 3/6/2015 | 3/11/2015 | 3/11/2015 1:50:56 PM | P | DONE |
|
|
Please call ahead for access - Gary Phone #: ###-#### Discussed wiring for bathroom remodel, dedicated 20 amp for receptacle.
|
ELE15-00517
| Electrical Rough-In | 3/11/2015 | 3/11/2015 | 3/11/2015 1:37:03 PM | P | PASS |
|
|
Please inspect walls for cover. Phone #: ###-#### Inspection requested via web by Spencer McLean Wall and hardlid rough in ok cover
|
ELE15-00542
| Permanent Service | 3/11/2015 | 3/11/2015 | 3/11/2015 1:09:52 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Needed final
|
ELE15-00542
| Final | 3/11/2015 | 3/11/2015 | 3/11/2015 1:09:40 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Contractor found no open splices in attic and installed handle ties for multi-wire branch circuits. Final ok
|
ELE15-00650
| Final | 3/11/2015 | 3/11/2015 | 3/11/2015 12:54:37 PM | P | PASS |
|
|
Larry Phone #: ###-#### Underground service lateral repaired, expansion joint installed. Final ok
|
ELE15-00390
| Final | 3/10/2015 | 3/11/2015 | 3/11/2015 12:31:52 PM | A | NR |
|
|
Call Jeff Gooch if gate should be locked. It was unlocked as of 9 Mar 2015 Phone #: ###-#### Inspection requested via web by Jeff Gooch Will need to test GFCI protection for final .
|
ELE14-02952
| Permanent Service | 3/10/2015 | 3/11/2015 | 3/11/2015 11:41:46 AM | A | PASS |
|
|
Need the 2nd meter location inspected so we can have a meter set thank you Phone #: ###-#### Inspection requested via web by Brad Baker 42k rated mains 7955 max available fault current contractor to post available fault current. Ground rod added. Unit 112 p/s u/g n ok
|
ELE15-00390
| Permanent Service | 3/11/2015 | 3/11/2015 | 3/11/2015 11:06:20 AM | P | PASS |
|
|
Call Jeff Gooch if gate should be locked. It was unlocked as of 9 Mar 2015 Phone #: ###-#### Inspection requested via web by Jeff Gooch p/s o/h n ok
|
ELE15-00657
| Electrical Rough-In | 3/10/2015 | 3/11/2015 | 3/11/2015 10:38:19 AM | A | PASS |
|
|
trench and electrical rough in of new shop/detached building. I need to put main breaker kit in new panel in shop, supply house gave be wrong kit. hooked power up to give temporary power. Phone #: ###-#### Inspection requested via web by steve sellers Underground and shop rough in ok cover
|
ELE15-00642
| Electrical Rough-In | 3/10/2015 | 3/11/2015 | 3/11/2015 10:05:45 AM | A | PASS |
|
|
Please inspect under-slab conduits. Phone #: ###-#### Inspection requested via web by Lynn Proctor Spa type business. Under slab rough in ok cover
|
ELE15-00643
| Temporary Service | 3/10/2015 | 3/11/2015 | 3/11/2015 9:50:34 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
|
ELE15-00269
| Final | 3/10/2015 | 3/11/2015 | 3/11/2015 9:33:30 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey Final ok
|
ELE15-00542
| Final | 3/10/2015 | 3/11/2015 | 3/11/2015 9:20:44 AM | A | FAIL |
|
|
Cameron-call for access Phone #: ###-#### Handle ties for multi-wire branch circuits and contractor to check kitchen wiring to ensure no open splices are visible in attic. All due to MIS14-00273, MIS14-00314, and ELE14-00698
|