Inspections for the day of: Friday, March 11, 2016.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00547 Electrical Rough-In3/11/20163/11/20163/11/2016 2:14:05 PMPPASS
kitchen wiring Phone #: ###-#### Inspection requested via web by Andrea Creek correction fixed for sink wall only ok cover
ELE16-00758 Rough-In Permanent Service3/10/20163/11/20163/11/2016 1:36:56 PMPPASS
Phone #: ###-#### Inspection requested via web by Shaun Kirkman rough-in ok cover p/s o/h n ok
ELE15-03656 Final3/11/20163/11/20163/11/2016 12:54:09 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender corrections fixed final ok
ELE16-00329 Electrical Rough-In3/10/20163/11/20163/11/2016 12:13:15 PMPPASS
Roger Bachman Phone #: ###-#### Inspection requested via web by Kerri Hamilton 3rd floor walls only ok cover
ELE15-03119 Electrical Rough-In3/11/20163/11/20163/11/2016 11:50:03 AMPFAIL
Jay Phone #: ###-#### 590.6 GFCI protection for temporary installation
ELE15-04068 Final3/10/20163/11/20163/11/2016 11:19:57 AMAPASS
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson final ok
ELE16-00668 Rough-In Permanent Service3/10/20163/11/20163/11/2016 11:19:35 AMAPASS
Rough in Phone #: ###-#### Inspection requested via web by Zane Robertson rough-in ok cover p/s u/g n ok
ELE16-00611 Conference3/10/20163/11/20163/11/2016 10:56:17 AMPCANC
I will be home around 3:45 on March 11th Friday. Thank you Dayrl DeGrange Phone #: ###-#### Inspection requested via web by Todd Ellioiott reschudule for monday
ELE16-00311 Final3/11/20163/11/20163/11/2016 10:47:51 AMAFAIL
Phone #: ###-#### Inspection requested via web by kendall bender 680.21 all pool pumps shall have GFCI protection
ELE15-03656 Final3/11/20163/11/20163/11/2016 10:37:14 AMAFAIL
Phone #: ###-#### Inspection requested via web by kendall bender 210.8 receptacles in a garage shall have GFCI protection/receptacles within 6' of a ink shall have GFCI protection 406.5 receptacles shall be rigidly mounted 406.4 tamper resistant receptacles required 314.27 floor boxes shall be listed fr application faceplate for back w/p
ELE15-02742 Final3/11/20163/11/20163/11/2016 9:16:10 AMPPASS
Phone #: ###-#### Inspection requested via web by Brandon Hillman corrections fixed final ok
ELE16-00738 Rough-In Permanent Service3/10/20163/11/20163/11/2016 9:08:14 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough-in ok cover p/s u/g n ok
ELE15-03639 Rough-In Permanent Service3/10/20163/11/20163/11/2016 9:01:44 AMACANC
Phone #: ###-#### Inspection requested via web by Brandon Hillman wrong address
ELE16-00181 Rough-In Permanent Service3/11/20163/11/20163/11/2016 9:01:08 AMPPASS
rough-in ok cover p/s u/g n ok