Inspections for the day of: Monday, March 11, 2019.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00117 Conference3/11/20193/11/20193/11/2019 3:31:12 PMPDONE
Contractor called to inform tile contractor buried floor heat in thin set. Instructed to remove around cold lead splice so we can verify it is positioned in floor as needed.
ELE18-03892 Final3/11/20193/11/20193/11/2019 1:45:38 PMPPASS
Etta Phone #: ###-#### Final ok
ELE19-00117 Electrical Rough-In3/11/20193/11/20193/11/2019 11:07:49 AMAFAIL
Looking for ok to cover floor heat in downstairs master bath. Lock box on front door, code is 1980 Phone #: ###-#### Inspection requested via web by Dean Gernaat
110.3- Manufacturers instructions state cold lead splice must be located in floor. Shall not be located in or on wall.
ELE18-01608 Electrical Rough-In3/8/20193/11/20193/11/2019 10:28:56 AMAPASS
Underground from main service to E.O. Wilson building Phone #: ###-#### Inspection requested via web by Mike McCarrel
EO wilson feeders and branch conduits rough in ok cover
ELE18-03928 Final3/9/20193/11/20193/11/2019 9:32:17 AMAFAIL
lock box code 2011 Phone #: ###-#### Inspection requested via web by Charles Davis
210.52(C)- For counter top areas in dining room area receptacle outlets shall be installed so that no point measured along wall line is more than 24" from a receptacle outlet. Island not set yet.
314.25- All boxes shall have covers. Furnace box mounted on side needs cover.
410.22- Luminaire boxes shall be covered. Light over sink hanging on wires.