ELE19-00725
| Permanent Service | 3/11/2019 | 3/11/2019 | 3/11/2019 1:56:52 PM | P | PASS |
|
|
Sean Phone #: ###-####... p/s o/h reconnect ok
|
ELE19-00838
| Rough-In Permanent Service | 3/11/2019 | 3/11/2019 | 3/11/2019 1:27:57 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer... 1..temp outlets installed with screws not approved for box...box shall be replaced..110.3 2..wire shall be free of pinch points and away from truss gang nailers...throughout house..110.12 3..NM cable shall be supported to code...334.30 every 4 1/2 ft. mst bedroom, entry, above panel 4..smoke detectors shall be made up-grounds connected
|
ELE19-00198
| Final | 3/11/2019 | 3/11/2019 | 3/11/2019 11:56:08 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt... corrections made...ok to final
|
ELE18-03476
| Electrical Rough-In | 3/8/2019 | 3/11/2019 | 3/11/2019 10:34:13 AM | A | PASS |
|
|
Zack Phone #: ###-####... Area E admin...as marked on plans
|
ELE19-00647
| Final | 3/4/2019 | 3/11/2019 | 3/11/2019 9:51:13 AM | A | PASS |
|
|
Homeowner: Patrick and Karen Lee ###-#### (Karen) Blue Raven Install Manager (project questions): Brian Prussia ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting... labelling, disconnect, and OCPD..ok
|
ELE19-00760
| Electrical Rough-In | 3/8/2019 | 3/11/2019 | 3/11/2019 8:39:00 AM | A | PASS |
|
|
Ceiling inspection. Von is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...ceiling grid and power poles ok
|
ELE16-01326
| Final | 3/11/2019 | 3/11/2019 | 3/11/2019 8:21:29 AM | A | PASS |
|
|
trailer owner non compliant...closing permit
|
ELE16-02136
| ELE-Aging Inspection | 3/11/2019 | 3/11/2019 | 3/11/2019 8:03:13 AM | | FAIL |
|
|
contractor needs to schedule inspection of fixed circuits and final of service
|
MIS19-00057
| ELE-Final | 3/11/2019 | 3/11/2019 | 3/11/2019 7:17:15 AM | A | PASS |
|
|
permit was pulled ELE19-00805 inspected and resulted 3/7/19
|