Inspections for the day of: Wednesday, March 11, 2020.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC20-00949 Final3/5/20203/11/20203/11/2020 3:34:16 PMPPASS
INSTALLER GERRY ###-#### UNIT #4 Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co locking caps ok- unit #4
MEC20-00879 Rough-in3/10/20203/11/20203/11/2020 2:23:51 PMPFAIL
mec and firepl Phone #: ###-#### Inspection requested via web by Oleg Chervak-
7200
1- need to resubmit man j carrier equipment installed shows payne on man j
2- gas test at zero
3- need insulation shield installed on fireplace flue 1st floor in joist bay and secure flue in chase above fireplace
4- need to seal transfer boots
5- remove metal thimble second floor attic and replace with flat metal and insulation shield needs 1" clearance to flue

7226
1- need to resubmit man j carrier equipment installed show payne on man j
2- fireplace needs secured to structure and flue needs secure to structure aboce fireplace in chase
3- need to seal transfer boots 1st floor
4- remove metal thimble piece in attic and replace with flat metal and insulation shield needs 1" clearance to flue
5 flue test at zero

left notices front room window both units
MEC20-00879 Pressure Test3/10/20203/11/20203/11/2020 2:14:58 PMPFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 7200 gas test fail at 3psi- flue test pass- 7226 20lb gas pass tagged meter location- flue test at zero
MEC20-00984 Rough-in3/10/20203/11/20203/11/2020 1:45:09 PMPFAIL
mec and firepl Phone #: ###-#### Inspection requested via web by Oleg Chervak-

7238
1- need to resubmit man j carrier equipment(furnace/ac) installed and shows payne on man j
2- need to secure fireplace flue to structure 1st floor chase above fireplace
3- firecaulk missing 2nd floor at floor on fireplace flue
4- insulation shield needs 1" clearance and flue needs 1" clearance to wood in attic/ remove metal in attic around fireplace flue and replace with flat metal in place has piece from thimble and firecaulk all the way around pipe
5- missing seal on supply duct 2nd floor on both seams in chase
6- exposed insulation in crawl needs vapor barrier/taped at crawl entrance
7- need to seal transfer boots 1st floor
left notice front window

7252
1- need to resubmit man j carrier equipment (furnace/ac) installed and man j shows payne
2- need to secure fireplace flue to structure 1st floor chase above fireplace
3- need to seal transfer boots 1st floor
4- draft stop 2nd floor on fireplace flue has gap need to be flush with floor not up on one side of 2x4 and seal open hole in attic draft stop 5- need intakeon furnace needs ran to attic or outside since in house
left notice front window
MEC20-00984 Pressure Test3/10/20203/11/20203/11/2020 1:25:38 PMPPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass both units tagged meter location- 5lb flue pass both inits
MEC20-00876 Final3/10/20203/11/20203/11/2020 11:23:10 AMAPASS
10:30 am pressure test for El-Ada #A-12972; Repeat final inspection as well (per phone call with Brian) Phone #: ###-#### Inspection requested via web by Loren Bailey- furnace a/c coil co locking caps ok- 5lb flue pass
MEC20-00748 Final3/10/20203/11/20203/11/2020 10:20:34 AMAPASS
call harriet when on the way ###-####
Phone #: ###-#### Inspection requested via web by Lindsey Stegemann- fireplace final ok
MEC20-00610 Rough-in3/10/20203/11/20203/11/2020 9:26:14 AMAPASS
duct seal inspection in new room in front of building by customer service Phone #: ###-#### Inspection requested via web by Steve Torgerson- R/I ok- seal on supply and return ducting ok- ok to insulate- registers ok
MEC20-00991 Rough-in3/9/20203/11/20203/11/2020 8:47:21 AMAPASS
CALL FOR ACCESS ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- R/I ok
MEC20-00991 Final3/11/20203/11/20203/11/2020 8:47:07 AMAPASS
CALL FOR ACCESS ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- final ok- non combustible surround and mantel existing
MEC20-00991 Pressure Test3/9/20203/11/20203/11/2020 8:46:23 AMAPASS
CALL FOR ACCESS ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- 20lb gas pass
MIS20-00065 MEC-Conference2/26/20203/11/20203/11/2020 8:07:15 AMANH
check on permit status- no one on job site- correction still posted on front door-