FIR19-00353
| INSP-Final Inspection | 3/11/2020 | 3/11/2020 | 3/11/2020 3:16:30 PM | P | CANC |
|
|
Not ready for final until the interconnection with the fire alarm has been tested. Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR19-00353
| INSP-Sprinkler Rough-in | 3/11/2020 | 3/11/2020 | 3/11/2020 3:14:38 PM | P | PASS |
|
|
The remaining sprinkler piping on the first floor is ok for cover. Forward flush test passed.
|
FIR19-00353
| INSP-Sprinkler Rough-in/Hydro | 3/11/2020 | 3/11/2020 | 3/11/2020 3:13:56 PM | P | PASS |
|
|
The overhead hydro's passed. Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR19-00853
| INSP-Alarm Testing | 3/10/2020 | 3/11/2020 | 3/11/2020 12:00:48 PM | P | NR |
|
|
Plan mods are needed showing the correct fire alarm panel model installed and the correct means of communication installed. These items currently do not match the approved plans. No testing performed.
Phone #: ###-#### Inspection requested via web by John Lopez
|
BLD20-00130
| FIRE-Final Inspection | 3/10/2020 | 3/11/2020 | 3/11/2020 10:14:32 AM | A | PASS |
|
|
Life safety passed.
Matt Phone #: ###-####
|
FIR20-00052
| INSP-Final Inspection | 3/10/2020 | 3/11/2020 | 3/11/2020 10:14:10 AM | A | PASS |
|
|
Permit finaled.
Phone #: ###-#### Inspection requested via web by Jonathan LaFond
|