FIR19-00845
| INSP-Final Inspection | 3/11/2020 | 3/11/2020 | 3/11/2020 3:02:56 PM | P | FAIL |
|
|
Exterior sidewall heads are to close to deck, minimum of 4 inches, not more than 6 inches from deck is the requirement for sidewalls per NFPA13.
Raul is contact Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00954
| INSP-Final Inspection | 3/9/2020 | 3/11/2020 | 3/11/2020 3:01:50 PM | P | FAIL |
|
|
Elevator was inop at time of inspection, elevator was out of service due to elevator inspection not being completed yet.
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
FIR19-00845
| INSP-Sprinkler Rough-in/Hydro | 3/11/2020 | 3/11/2020 | 3/11/2020 3:00:58 PM | P | DONE |
|
|
Temporary heat was removed before temp heat was established. As discussed, if temp heat was removed and building reached below 40 degrees then a re-hydro will be required, re-hydor has been witnessed with no observed pressure loss at riser provided gauges.
Raul is contact Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR20-00056
| INSP-Conference | 3/9/2020 | 3/11/2020 | 3/11/2020 2:58:53 PM | A | DONE |
|
|
Fire conference complete.
Inspection requested via web by Ken Webster
|
FIR20-00063
| INSP-Sprinkler Rough-in | 3/11/2020 | 3/11/2020 | 3/11/2020 11:41:41 AM | P | PART |
|
|
Rough in inspection complete, piping between conditioned spaces approved for cover. No tenting installed at time of inspection, piping requiring tenting not approved for cover.
Tenting and overhead rough, call James before heading out. Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-02691
| FIRE-Final Inspection | 3/10/2020 | 3/11/2020 | 3/11/2020 11:26:28 AM | A | FAIL |
|
|
Wall layout by breakroom area does not city approved drawings. Notated 2 areas that show exit sign/emergency lighting location but exit signs/emergency lighting are not in the city approved plan location. Provide exit discharge emergency illumination per note 12 on the building permit fire code review comments.
Back door lock box code is 1208 Phone #: ###-#### Inspection requested via web by Josh Strasser
|
FIR20-00075
| INSP-Sprinkler Rough-in | 3/10/2020 | 3/11/2020 | 3/11/2020 10:55:51 AM | A | PASS |
|
|
Previously noted item has been corrected, cover is approved, sticker placed approval.
Tenting inspection. Call Anthony before heading out. Thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
BLD19-01927
| FIRE-Final Inspection | 3/10/2020 | 3/11/2020 | 3/11/2020 10:39:54 AM | A | FAIL |
|
|
Could not test release function on north stairwell door due to wiring issue, will need to retest release after repair is made.
Test remote unlock switch for L5 stairwell doors. Phone #: ###-#### Inspection requested via web by Sam Reading
|
FIR19-00538
| INSP-Final Inspection | 3/9/2020 | 3/11/2020 | 3/11/2020 10:38:55 AM | A | FAIL |
|
|
Communicator battery trouble did not annunciate at the panel or report with monitoring.
Ken Pieron, Technician Phone #: ###-#### Inspection requested via web by John Siewert
|
FIR19-00537
| INSP-Final Inspection | 3/9/2020 | 3/11/2020 | 3/11/2020 10:38:35 AM | A | FAIL |
|
|
Communicator battery trouble did not annunciate at the panel or report with monitoring.
Ken Pieron, Technician Phone #: ###-#### Inspection requested via web by John Siewert
|
FIR19-00540
| INSP-Final Inspection | 3/6/2020 | 3/11/2020 | 3/11/2020 10:16:17 AM | A | PASS |
|
|
Final fire sprinkler inspection is complete.
Robert Chambers is the contact.Thanks! (: Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR19-00551
| INSP-Final Inspection | 3/6/2020 | 3/11/2020 | 3/11/2020 10:15:13 AM | A | PASS |
|
|
Final fire sprinkler inspection is complete.
Robert Chambers is the contact. Thanks! (: Phone #: ###-#### Inspection requested via web by Stan Beus
|