BLD00-01498
| FIRE-Final Inspection | 3/11/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 03/11/2002 at 12:53:16. Contact: ###-####.
|
BLD01-03169
| FIRE-Alarm Testing | 3/11/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 03/11/2002 at 14:04:22. Contact: ###-####. all new duct detectors tested and shut down AHU's; no alarm plans 3/12/2002 4:26:03 PM
|
BLD01-02637
| FIRE-Final Inspection | 3/11/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | A | PASS |
|
|
###-#### WAYNE
|
FIR02-00042
| INSP-Sprinkler Rough-in | 3/12/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | A | FAIL |
|
|
Added by Inspector: 409 On 3/12/2002 8:50:49 AM QR heads used on new line in storage room - not per plans
|
BLD01-03049
| FIRE-Final Inspection | 3/11/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | A | FAIL |
|
|
fire fn john- ###-#### overhead door at loading tested for release with fusible link and operated properly. QR sprinklers 155 temp used in storage room on new line, not per plans 3/12/2002 8:49:48 AM
|
FIR01-00427
| INSP-Supply line flush | 3/11/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 03/11/2002 at 12:25:12. Contact: ###-####. flow still very low 3/12/2002 4:26:52 PM
|
FIR02-00069
| INSP-Final Inspection | 3/12/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | P | FAIL |
|
|
rob ###-#### fn need custom labels for all address points on new panel 3/12/2002 4:26:34 PM
|
BLD00-01563
| FIRE-Final Inspection | 3/12/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | P | PASS |
|
|
I show the sprinkler permit finaled but not life safety.
|
FIR01-00555
| INSP-Final Inspection | 3/12/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by Inspector: 409 On 3/12/2002 12:50:48 PM
|
BLD01-03048
| FIRE-Final Inspection | 3/12/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by Inspector: 409 On 3/12/2002 1:30:05 PM
|
FIR01-00615
| INSP-Final Inspection | 3/12/2002 | 3/12/2002 | 3/12/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 3/12/2002 1:30:54 PM
|