Inspections for the day of: Wednesday, March 12, 2003.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00454 INSP-Sprinkler Rough-in3/10/20033/12/20033/12/2003 12:00:00 AMAPART
brad; Phone #: ###-#### Internet Inspection Request from: Annette Moore hydro okay on low pressure side 3/12/2003 1:02:36 PM
BLD02-01949 FIRE-Final Inspection3/11/20033/12/20033/12/2003 12:00:00 AMAPASS
RON; Phone #: ###-#### Internet Inspection Request from: Darla Downs fire sprinkler riser room requires penetration fire stopping due to room being a 1 hr room for sprinkler control valve inside room; Ron will have patched for structural inspector 3/12/2003 9:23:12 AM
FIR03-00098 INSP-Final Inspection3/11/20033/12/20033/12/2003 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 3/11/2003 at 2:24:43 PM. Contact: ###-####.
BLD02-03022 FIRE-Final Inspection3/11/20033/12/20033/12/2003 12:00:00 AMAPASS
###-#### call first to meet there all strcutural work 3/12/2003 10:18:40 AM
BLD03-00100 FIRE-Final Inspection3/11/20033/12/20033/12/2003 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 3/11/2003 at 6:22:19 PM. Contact: ###-####. fire sprinklers overspaced at east side of new wall; need to verify candela rating of horn/strobe intraining room - minimum of 110 cd needed 3/12/2003 2:47:28 PM
FIR02-00419 INSP-Final Inspection3/12/20033/12/20033/12/2003 12:00:00 AMAPASS
FIR02-00449 INSP-Final Inspection3/12/20033/12/20033/12/2003 12:00:00 AMAPASS
Gentex chime/strobes installed and installed per listing
BLD02-03004 FIRE-Final Inspection3/12/20033/12/20033/12/2003 12:00:00 AMAPASS
FIR03-00100 INSP-Final Inspection3/12/20033/12/20033/12/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 3/12/2003 at 10:55:54 AM. Contact: ###-####.
FIR03-00069 INSP-Sprinkler Rough-in3/12/20033/12/20033/12/2003 12:00:00 AMPPART
UG stub out 5 ft okay per plans 3/12/2003 2:49:10 PM
BLD02-02640 FIRE-Final Inspection3/12/20033/12/20033/12/2003 12:00:00 AMPPASS
MIS02-00188 FIR-Final3/12/20033/12/20033/12/2003 12:00:00 AMPPASS
FIR03-00092 INSP-Final Inspection3/12/20033/12/20033/12/2003 12:00:00 AMPPASS
###-####