FIR02-00466
| INSP-Final Inspection | 3/10/2003 | 3/12/2003 | 3/12/2003 12:00:00 AM | A | FAIL |
|
|
Could not test the valve because no one could find the key for the chain lock 3/12/2003 3:16:14 PM
|
BLD02-02800
| FIRE-Final Inspection | 3/10/2003 | 3/12/2003 | 3/12/2003 12:00:00 AM | A | FAIL |
|
|
Provide approved hardware on the office and storage room doors. Repair emergency light. Relocate pendant from supply register or provide higher temp. Provide air balance reports. Main fire alarm system is not finaled yet 3/12/2003 10:43:47 AM
|
BLD02-02800
| FIRE-Alarm Testing | 3/10/2003 | 3/12/2003 | 3/12/2003 12:00:00 AM | A | FAIL |
|
|
Provide approved hardware on the office and storage room doors. Repair emergency light. Relocate pendant from supply register or provide higher temp. Provide air balance reports. Main fire alarm system is not finaled yet 3/12/2003 10:43:55 AM
|
BLD03-00260
| FIRE-Final Inspection | 3/11/2003 | 3/12/2003 | 3/12/2003 12:00:00 AM | A | FAIL |
|
|
robert; Phone #: ###-#### Replace the painted sprinkler pendant in storage room 109 or remove it. Repair the exit/emergency light in the spa corridor. Add emergency light in the spa. Provide atleast three more fire extinguishers. Retag the existing fire extinguisher. Verify current inspection on the fire sprinkler system. Remove thumbturns on the rear exit doors. Remove the dead bolts on the main entry/exit. Replace the door hardware on restrooms 107, 113, 114 and the closet next to 113. 3/12/2003 10:36:57 AM
|
BLD02-02761
| FIRE-Conference | 3/11/2003 | 3/12/2003 | 3/12/2003 12:00:00 AM | A | DONE |
|
|
pendant in front of space is still overspaced and the fire alarm plans are still an issue 3/12/2003 9:17:39 AM
|
FIR03-00046
| INSP-Final Inspection | 3/12/2003 | 3/12/2003 | 3/12/2003 12:00:00 AM | A | PASS |
|
|
Type 1 hood operated correctly and reported to the main fire alarm panel.
|
FIR02-00512
| INSP-Alarm Testing | 3/12/2003 | 3/12/2003 | 3/12/2003 12:00:00 AM | P | PART |
|
|
finished testing the duct smoke detectors and the fire sprinkler riser in Ross. Need to finish the other sprinkler risers and panel items
|
BLD02-02761
| FIRE-Conference | 3/12/2003 | 3/12/2003 | 3/12/2003 12:00:00 AM | P | PART |
|
|
A temporary occupancy was given with dave millers permission until the fire alarm plans have been approved and the changes made and inspected 3/12/2003 3:49:32 PM
|