Inspections for the day of: Friday, March 12, 2004.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00040 FIRE-Final Inspection3/11/20043/12/20043/12/2004 12:00:00 AMAPASS
fire life safety finaled 3/12/2004 9:57:36 AM
FIR03-00569 INSP-Alarm Testing3/11/20043/12/20043/12/2004 12:00:00 AMAFAIL
Inspection was set up for 8:15 and the contractor did not show up. I called and left him a message that I was here. 3/12/2004 8:29:53 AM
FIR03-00667 INSP-Supply line flush3/11/20043/12/20043/12/2004 12:00:00 AMAPASS
Underground flush is ok 3/12/2004 1:47:23 PM
FIR03-00668 INSP-Supply line flush3/11/20043/12/20043/12/2004 12:00:00 AMAPASS
Underground flush is ok 3/12/2004 1:47:04 PM
BLD03-02027 FIRE-Final Inspection3/11/20043/12/20043/12/2004 12:00:00 AMAPASS
Fire life safety finaled 3/12/2004 11:33:47 AM
FIR03-00806 INSP-Sprinkler Rough-in/Hydro3/11/20043/12/20043/12/2004 12:00:00 AMAPASS
hydro test on the dry pipe riser is OK 3/12/2004 11:20:23 AM
BLD03-02290 FIRE-Final Inspection3/11/20043/12/20043/12/2004 12:00:00 AMAPASS
fire life safety finaled 3/12/2004 8:49:13 AM
BLD03-02292 FIRE-Final Inspection3/11/20043/12/20043/12/2004 12:00:00 AMAPASS
fire life safety finaled 3/12/2004 8:49:25 AM
FIR04-00074 INSP-Final Inspection3/12/20043/12/20043/12/2004 12:00:00 AMAPASS
fire sprinklers finaled
BLD03-02908 FIRE-Final Inspection3/11/20043/12/20043/12/2004 12:00:00 AMAPASS
fire life safety finaled 3/12/2004 9:03:11 AM
FIR04-00136 INSP-Final Inspection3/12/20043/12/20043/12/2004 12:00:00 AMAPART
A temporary occupancy was given with dave millers permission until the fire alarm system is finaled.
FIR03-00214 FIR-Aging Inspection3/12/20043/12/20043/12/2004 12:00:00 AMPPASS
underground flush ok 3/12/2004 4:29:01 PM
FIR03-00511 INSP-Final Inspection3/12/20043/12/20043/12/2004 12:00:00 AMPFAIL
General contractor did not have the approved resubmitted plans on site for the inspection 3/12/2004 3:02:08 PM
MIS04-00077 FIR-Final3/12/20043/12/20043/12/2004 12:00:00 AMPPASS
Life safety finaled 3/12/2004 11:00:11 AM
FIR03-00816 INSP-Supply line flush3/12/20043/12/20043/12/2004 12:00:00 AMPCANC
Wrong permit number. See fir03-00667 3/12/2004 1:44:31 PM
FIR04-00123 INSP-Supply line flush3/12/20043/12/20043/12/2004 12:00:00 AMPCANC
Wrong permit number called in. See fir03-00668 3/12/2004 1:43:55 PM
BLD04-00376 FIRE-Final Inspection3/12/20043/12/20043/12/2004 12:00:00 AMPCANC
CURT; Phone #: ###-#### Internet Inspection Request from: Darla Downs
BLD03-03068 FIRE-Final Inspection3/12/20043/12/20043/12/2004 12:00:00 AMPPART
A temporary occupancy was given with dave millers permission until the fire alarm system is finaled. All life safety items are ok to be finaled when alarm system is complete. 3/12/2004 11:35:32 AM
FIR03-00659 INSP-Sprinkler Rough-in/Hydro3/11/20043/12/20043/12/2004 12:00:00 AMPFAIL
Hydro test failed. Cracked pipe. 3/12/2004 2:51:01 PM
FIR03-00659 INSP-Final Inspection3/11/20043/12/20043/12/2004 12:00:00 AMPFAIL
Provide spare sprinkler heads in head cabinet. Provide signage. Verify pressure relief vavle. Hydro test system. Tag new sprinkler system. Verify inspection tag for the existing fire sprinkler system and fire pump is current. Finish earth quake bracing. 3/12/2004 2:53:46 PM