Inspections for the day of: Monday, March 12, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04521 ELE-Aging Inspection3/12/20073/12/20073/15/2007 3:30:01 PM DONE
called contr to check status of permit
ELE07-00008 Final3/12/20073/12/20073/12/2007 3:27:37 PMPNH
candy or sharon - pls call for secaurity code; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called for code, no lock box, need to call when available
ELE07-00114 Electrical Rough-In3/12/20073/12/20073/12/2007 2:17:23 PMPFAIL
Final - if you have questions pls call Mike @ ###-####. Thank! Scheduled by Heather W/ Doherty Phone #: ###-#### called, left messag, left corr notice, nec 408.4 circuit directory shall be clear, concise, and legibly identified, with circuits specific, 110.12(A) ,408.&, unused openings in panels shall be closed, 240.81 circuit breaker handle shall be up for on and down for off, 406.5 recpt faceplates shall completely cover openings, 330.30(B) mc cable shall be strapped within 12" of box, 358.30(A) emt shall be strapped within 3' of box, 422.31(B) shall provide disconnect or lockout for appliances, water heater, 250.104(A) h & c water piping shall be bonded, 110.26 there shall be no foreign piping in work space about equipment, BCC all make-up shall be done-below service panel,all equipment shall be listed by a nationally recognized testing laboratory (furniture), and all covers installed, meter shall be weatherproof
ELE07-00811 Final3/12/20073/12/20073/12/2007 12:46:37 PMPPASS
Work performed by Steve Johnson. Phone #: ###-#### p/s o/h rec ok, talked to elect to provide abrasion protection for gec at service panel
ELE07-00775 Rough-In Permanent Service3/12/20073/12/20073/12/2007 10:32:48 AMAPASS
Phone #: ###-#### ric ok, p/s u/g n ok, 4 meters
ELE07-00692 Rough-In Permanent Service3/9/20073/12/20073/12/2007 9:48:26 AMACANC
Phone #: ###-#### see ri and p/s
ELE07-00692 Electrical Rough-In3/12/20073/12/20073/12/2007 9:45:08 AMAFAIL
Phone #: ###-#### called contr, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 250.86 all metal boxes shall be grounded, 300.14 at least 6" of free conductor shall be provided at each box, 314.16 boxes shall be of sufficient size to provide free space for conductors (rear garage pan with 2 nm cables), BCC all make-up shall be done, all u/g shall be inspected before cover
ELE07-00692 Permanent Service3/12/20073/12/20073/12/2007 9:40:31 AMAPASS
Phone #: ###-#### p/s u/g n ok
ELE07-00153 Final3/9/20073/12/20073/12/2007 8:57:31 AMACANC
###-####
THANK YOU. Phone #: ###-#### x0000 called number, didn't know about job, called office,got elect number, called, he was quite a way out and needs to meet on job, said to call for another inspection and set up appointment to meet elect
ELE07-00798 Final3/9/20073/12/20073/12/2007 8:34:25 AMAPASS
vern - across the street from storage facility; Phone #: ###-#### Internet Inspection Request from: Victoria Beall see p/s, ok to final, called contr on address
ELE07-00798 Permanent Service3/12/20073/12/20073/12/2007 8:33:10 AMAPASS
vern - across the street from storage facility; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s u/g n ok
ELE05-04325 Final3/9/20073/12/20073/12/2007 8:16:19 AMAPART
Jason; Phone #: ###-#### Internet Inspection Request from: Stacie Backus kitchen area ok to final anop