MEC06-04044
| Pressure Test | 3/12/2007 | 3/12/2007 | 3/12/2007 5:12:34 PM | P | NR |
|
|
###-####..leaks..glycol test for solar heat
|
MEC06-03660
| Final | 3/12/2007 | 3/12/2007 | 3/12/2007 4:21:18 PM | P | NR |
|
|
Please call Gary with any questions ###-#### Phone #: ###-####
|
MEC07-00808
| Rough-in | 3/12/2007 | 3/12/2007 | 3/12/2007 3:44:06 PM | P | PASS |
|
|
Homeowner will be home for you. Thanks, Andrea. Phone #: ###-#### x0000
|
MEC06-02978
| Final | 3/9/2007 | 3/12/2007 | 3/12/2007 3:20:21 PM | P | FAIL |
|
|
Phone #: ###-####..left c/n with home-owner
|
MEC06-00165
| Final | 3/12/2007 | 3/12/2007 | 3/12/2007 2:33:15 PM | P | PASS |
|
|
###-####
|
MEC07-00492
| Rough-in | 3/9/2007 | 3/12/2007 | 3/12/2007 2:26:38 PM | A | PASS |
|
|
nick ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith..corrections made..thanks
|
MEC07-00332
| Rough-in | 3/12/2007 | 3/12/2007 | 3/12/2007 1:59:43 PM | P | PART |
|
|
###-#### brian..the duct wrap insulator will hold off on the first wrap until the hoods are hung
|
MEC07-00668
| Pressure Test | 3/9/2007 | 3/12/2007 | 3/12/2007 1:38:46 PM | A | PASS |
|
|
clint; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
MEC07-00668
| Rough-in | 3/9/2007 | 3/12/2007 | 3/12/2007 1:38:21 PM | A | PASS |
|
|
clint; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
MEC06-02738
| Rough-in | 3/9/2007 | 3/12/2007 | 3/12/2007 1:21:47 PM | A | PASS |
|
|
ON SITE CONTACT - CORRY HAZEN ###-####. INSPECTION REQUESTED BY JANE. Phone #: ###-####
|
MEC07-00737
| Pressure Test | 3/9/2007 | 3/12/2007 | 3/12/2007 11:12:12 AM | A | PASS |
|
|
parcel hold has nothing to do with mec..20lb ok
|
MEC07-00737
| Rough-in | 3/9/2007 | 3/12/2007 | 3/12/2007 11:10:28 AM | A | FAIL |
|
|
parcel hold has nothing to do with mec rough in..need to either pan off or shield b-vent from r/a duct in chase..does the furnace manuf require a min of 5' from the furn to the termination, and a 1/4" slope per foot? gas ok..it looked like there might be a screw penetrating the inner liner of the b-vent but i couldn't tell for sure..(poor eyesight ya know)..thanks
|
MEC07-00332
| Rough-in | 3/9/2007 | 3/12/2007 | 3/12/2007 10:53:01 AM | A | PART |
|
|
brian Note: grease duct; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles..washer and slag ground out of grease duct..waited for brian to arrive from his office
|
MEC06-03660
| Conference | 3/12/2007 | 3/12/2007 | 3/12/2007 10:18:13 AM | P | CANC |
|
|
Please call Gary with any questions ###-#### Phone #: ###-#### Inspection cancelled from web by: Sonja Hankel
|
MEC06-02716
| MEC-Aging Inspection | 3/12/2007 | 3/12/2007 | 3/12/2007 10:12:31 AM | | PASS |
|
|
work in progress
|
MEC06-01811
| MEC-Aging Inspection | 3/12/2007 | 3/12/2007 | 3/12/2007 10:11:06 AM | | PASS |
|
|
job just started////wip per g/c
|
MEC06-00165
| MEC-Aging Inspection | 3/12/2007 | 3/12/2007 | 3/12/2007 10:09:33 AM | | PASS |
|
|
troy passed this job..i'm not sure why it doesn't show it as such, i rescheduled it again and it should final it..thanks dixie
|
MEC07-00799
| Pressure Test | 3/12/2007 | 3/12/2007 | 3/12/2007 10:00:12 AM | P | PASS |
|
|
Please call Terry with any questions ###-#### Phone #: ###-####..this should have been an am inspection..60lb test from meter to equipment ok
|
MEC07-00801
| Pressure Test | 3/12/2007 | 3/12/2007 | 3/12/2007 9:59:21 AM | P | PASS |
|
|
Please call Terry with any questions ###-#### Phone #: ###-####..this should have been an am inspection..60lb test ok from meter to equipment
|
MEC07-00800
| Pressure Test | 3/12/2007 | 3/12/2007 | 3/12/2007 9:58:22 AM | P | CANC |
|
|
Please call Terry with any questions ###-#### Phone #: ###-####..this should have been an am inspections..thanks
|
MEC06-04180
| Final | 3/9/2007 | 3/12/2007 | 3/12/2007 8:42:33 AM | A | PASS |
|
|
Customer requests to be first inspection of the day (8:00). Please call customer as early as possible to confirm. Thank you. Phone #: ###-####
|