FIR08-00025
| INSP-Sprinkler Rough-in | 3/11/2008 | 3/12/2008 | 3/12/2008 4:45:03 PM | P | PART |
|
|
See locations on approved plan set marked okay for cover at the lobby and elevator vestibules.
|
BLD06-03526
| FIRE-Final Inspection | 3/11/2008 | 3/12/2008 | 3/12/2008 4:31:14 PM | P | PASS |
|
|
Final fire life safety inspection completed acceptable.
|
BLD06-03521
| FIRE-Final Inspection | 3/11/2008 | 3/12/2008 | 3/12/2008 4:30:28 PM | P | PASS |
|
|
Noted correction items verified for completion, fire life safety finaled.
|
BLD06-03520
| FIRE-Final Inspection | 3/11/2008 | 3/12/2008 | 3/12/2008 4:29:26 PM | P | PASS |
|
|
Corrections are complete, fire life safety passed.
|
BLD06-03305
| FIRE-Final Inspection | 3/11/2008 | 3/12/2008 | 3/12/2008 4:28:41 PM | P | PASS |
|
|
Fire life safety inspection passed.
|
FIR07-00324
| INSP-Final Inspection | 3/12/2008 | 3/12/2008 | 3/12/2008 4:27:44 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
BLD06-00077
| FIRE-Final Inspection | 3/12/2008 | 3/12/2008 | 3/12/2008 4:00:20 PM | P | NR |
|
|
Need project fire sprinkler and alarm permits finaled prior to building life safety final.
|
BLD06-00076
| FIRE-Final Inspection | 3/12/2008 | 3/12/2008 | 3/12/2008 3:58:28 PM | P | NR |
|
|
Pending alarm and sprinkler finals.
|
FIR07-01043
| INSP-Final Inspection | 3/10/2008 | 3/12/2008 | 3/12/2008 3:55:42 PM | A | FAIL |
|
|
Descriptor for the new manual pull station is not accurate, need to provide an updated map at the panel reflecting correct floorplan and device locations, duct detectors could not be tested due to locked thermostat controls for the HVAC units, lock at the panel breaker installed while on site, one overspaced notification device repositioned while on site, 95cd ceiling mounted appliances not to exceed spacing guidelines, recommend lower decible settings at the restrooms due to sound pressure levels near 110 dBA at the minimum hearing distance, EOL voltage not tested at this time.
|
BLD07-03089
| FIRE-Final Inspection | 3/11/2008 | 3/12/2008 | 3/12/2008 11:04:07 AM | P | FAIL |
|
|
Missing signage at the terrace doors, exterior EM light did not function, not ready for final at this time.
|
FIR08-00160
| INSP-Sprinkler Rough-in/Hydro | 3/12/2008 | 3/12/2008 | 3/12/2008 11:01:44 AM | A | PART |
|
|
Sprinkler system modifications are approved for ceiling cover at locations annotated and initialed with todays date on stamped plan set.
|
FIR08-00079
| INSP-Final Inspection | 3/11/2008 | 3/12/2008 | 3/12/2008 10:29:28 AM | A | PASS |
|
|
Tie-in completed, tags and signage added while on site, fire sprinkler work approved for final.
|
FIR08-00078
| INSP-Final Inspection | 3/11/2008 | 3/12/2008 | 3/12/2008 10:26:38 AM | A | PASS |
|
|
Fire sprinkler passed final inspection, permit finaled.
|
FIR08-00128
| INSP-Final Inspection | 3/11/2008 | 3/12/2008 | 3/12/2008 10:24:09 AM | A | PASS |
|
|
Fire alarm system modifications passed field testing, permit finaled.
|
BLD05-02158
| FIRE-Final Inspection | 3/11/2008 | 3/12/2008 | | A | |
|
|
|