Inspections for the day of: Wednesday, March 12, 2008.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS07-00153 FIR-Conference3/5/20083/12/20083/17/2008 4:21:48 PMPDONE
As requested I stopped at this project to verify the the warehouse area and the storage racks were being utilized. I identified myself to the receptionist and requested access to the warehouse to verify if the racks were being used. I was granted access so I went to the warehouse and found that the racks were indeed being used. One of three gentleman in the warehouse asked if I needed help with anything. I stated to him that I didn't need any help and I identified myself to him and told him that I was a fire inspector and that I was there to verify if the racks were being used. I also told him that they were not supposed to be used. I also took three photos with my personal cell phone. I then met with sam rogers and went over the pictures and what I witnessed.
FIR08-00085 INSP-Sprinkler Rough-in3/12/20083/12/20083/12/2008 5:21:49 PMPPASS
The piping can be covered by the deco shield.
BLD07-02800 FIRE-Final Inspection3/12/20083/12/20083/12/2008 5:16:42 PMPPASS
life safety passed
FIR07-00578 INSP-Sprinkler Rough-in3/11/20083/12/20083/12/2008 3:14:25 PMAPASS
Need the fire proofing repaired in the storage area and the 401 canopies(heads lowered) installed as per discussion. The galvanized piping/fittings on the roof are ok as per discussion with Brian Johnson.
FIR08-00014 INSP-Final Inspection3/10/20083/12/20083/12/2008 3:12:11 PMPFAIL
Provide monitor module for the existing duct smoke detector and relocate the new duct smoke detector to the return side of the hvac unit. Location is marked on the plans. Also provide the monitoring station test reports for review.
FIR07-00575 INSP-Final Inspection3/11/20083/12/20083/12/2008 3:10:22 PMPPASS
Permit finaled
FIR08-00001 INSP-Final Inspection3/12/20083/12/20083/12/2008 1:34:34 PMPPASS
Permit finaled
FIR07-00918 INSP-Final Inspection3/12/20083/12/20083/12/2008 1:34:02 PMPPASS
permit finaled
BLD08-00421 FIRE-Final Inspection3/11/20083/12/20083/12/2008 10:04:17 AMAPASS
life safety passed