Inspections for the day of: Friday, March 12, 2010.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-00557 FIRE-Conference3/12/20103/12/20103/12/2010 4:54:11 PMPDONE
Tom, building inspector, and I spoke to Herd about fire blocking and fire sprinkler requirements at the two fireplace locations and the columns. Also the the entire south third of the building has been covered with out the sprinkler piping having been inspected. I notified Herd of IFC requirements but stated that for this one specific happening I would not require the ceiling to be removed but the insulation would be required to be removed from over the piping for an inspection. The insulation will then need to be reinstalled for a secondary inspection. Any areas that I deam accessible will have the ceilings removed for sprinkler piping inspection. I notified Scott of the situation.
FIR09-00711 INSP-Conference3/12/20103/12/20103/12/2010 4:48:49 PMPDONE
I spoke to Matt about duct smoke detector placement and possible manometer testing to verify correct function of the detectors.
BLD09-00379 FIRE-Final Inspection3/12/20103/12/20103/12/2010 3:31:08 PMPPASS
Life safety passed.
BLD09-00981 FIRE-Final Inspection3/11/20103/12/20103/12/2010 3:28:52 PMPFAIL
Provide occupant load sign and approved single action hardware on the south exit gate. Per Paul the exit gates shown on the plans at the north end of the wall will not be installed. Per the plan reviewer resubmitted plans are not required.
FIR10-00062 INSP-Sprinkler Rough-in3/11/20103/12/20103/12/2010 11:26:47 AMAPASS
The sprinkler piping can be covered.
BLD10-00431 FIRE-Final Inspection3/11/20103/12/20103/12/2010 12:00:00 AMACANC
jim Phone #: ###-####