BLD11-02974
| FIRE-Conference | 3/12/2012 | 3/12/2012 | 3/12/2012 3:39:10 PM | P | DONE |
|
|
Mike Jordan and I verified that the existing plywood sheating, at the store front, is indeed fire rated.
|
FIR11-00244
| INSP-Final Inspection | 3/8/2012 | 3/12/2012 | 3/12/2012 3:04:27 PM | A | FAIL |
|
|
Relocate the heat detector in the elevator shaft to within 2' of the sprinkler head, provide photo smoke detector in the first floor exterior entry as per plans, program for alternate floor recall when the machine room smoke detector is activated, provide firemans flashing hat per the drawings or remove the addressable relay/wiring/programming and provide as-built drawings showing the changes. See the city approved plans for locations marked in red.
|
BLD12-00022
| FIRE-Final Inspection | 3/9/2012 | 3/12/2012 | 3/12/2012 2:58:33 PM | A | PASS |
|
|
Life safety passed
|
BLD12-00115
| FIRE-Final Inspection | 3/9/2012 | 3/12/2012 | 3/12/2012 2:58:04 PM | A | PASS |
|
|
life safety passed
|
FIR08-00143
| INSP-Final Inspection | 3/8/2012 | 3/12/2012 | 3/12/2012 1:24:39 PM | A | PASS |
|
|
Permit finaled
|
FIR11-00607
| INSP-Sprinkler Rough-in | 3/9/2012 | 3/12/2012 | 3/12/2012 10:42:22 AM | A | FAIL |
|
|
The plans were locked up in the job trailer. General contractor was not on site. Could not perform inspection. Left message on Don's voice mail.
|