Inspections for the day of: Monday, March 12, 2012.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-02974 FIRE-Conference3/12/20123/12/20123/12/2012 3:39:10 PMPDONE
Mike Jordan and I verified that the existing plywood sheating, at the store front, is indeed fire rated.
FIR11-00244 INSP-Final Inspection3/8/20123/12/20123/12/2012 3:04:27 PMAFAIL
Relocate the heat detector in the elevator shaft to within 2' of the sprinkler head, provide photo smoke detector in the first floor exterior entry as per plans, program for alternate floor recall when the machine room smoke detector is activated, provide firemans flashing hat per the drawings or remove the addressable relay/wiring/programming and provide as-built drawings showing the changes. See the city approved plans for locations marked in red.
BLD12-00022 FIRE-Final Inspection3/9/20123/12/20123/12/2012 2:58:33 PMAPASS
Life safety passed
BLD12-00115 FIRE-Final Inspection3/9/20123/12/20123/12/2012 2:58:04 PMAPASS
life safety passed
FIR08-00143 INSP-Final Inspection3/8/20123/12/20123/12/2012 1:24:39 PMAPASS
Permit finaled
FIR11-00607 INSP-Sprinkler Rough-in3/9/20123/12/20123/12/2012 10:42:22 AMAFAIL
The plans were locked up in the job trailer. General contractor was not on site. Could not perform inspection. Left message on Don's voice mail.