Inspections for the day of: Wednesday, March 12, 2014.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-03552 Final3/12/20143/12/20143/12/2014 3:09:50 PMPPASS
Can you please call me ahead of time so I can make sure someone is there to let you in. Thanks mark Phone #: ###-#### >> Inspection requested via web by Mark Hennequin Final ok
ELE13-02057 Electrical Rough-In3/12/20143/12/20143/12/2014 2:26:50 PMPPASS
Robert. 3rd floor restroom rough-in. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy 1st floor apartment lobby walls and hard lid access panels will be needed for existing junction boxes and disconnects, 3rd floor bathrooms wall and hard lid rough in ok
ELE14-00588 Final3/12/20143/12/20143/12/2014 1:15:23 PMPPASS
Please provide a final inspection for the temporary power pole. Call Darrell with any questions. Thanks, Sean Phone #: ###-#### >> Inspection requested via web by Kevin Perez Temp pole final ok
ELE14-00588 Temporary Service3/12/20143/12/20143/12/2014 1:15:10 PMPPASS
Please provide a final inspection for the temporary power pole. Call Darrell with any questions. Thanks, Sean Phone #: ###-#### >> Inspection requested via web by Kevin Perez t/s o/h n ok
ELE14-00449 Final3/11/20143/12/20143/12/2014 12:37:02 PMAPASS
Please call Carlos if you have any questions. If no corrections please do a final Phone #: ###-#### >> Inspection requested via web by David Mackey Final ok
ELE14-00449 Permanent Service3/12/20143/12/20143/12/2014 12:09:58 PMPPASS
Please call Carlos if you have any questions. If no corrections please do a final Phone #: ###-#### >> Inspection requested via web by David Mackey p/s o/h n ok
ELE14-00157 Electrical Rough-In3/11/20143/12/20143/12/2014 10:16:21 AMAPASS
Ground work inspection. If you have any questions please contact Craig Timmons. Phone #: ###-#### >> Inspection requested via web by Vicki Moore North half under slab rough in ok cover
ELE14-00562 Final3/12/20143/12/20143/12/2014 9:52:10 AMAPASS
Rex
The Homeowner said the back gate will be good for you to go thru. Final ok

Mike Phone #: ###-#### >> Inspection requested via web by Mike Cole
ELE14-00437 Permanent Service3/11/20143/12/20143/12/2014 9:35:45 AMAFAIL
Erin or Dean-Please call at least 30 mins in advance of inspection Phone #: 412- 0527
230.28- Where service mast is used as support for overhead swing and it extends 3' or more past its support it shall have additional support.
250.90(B)- Metal nipple ran through concentric knockout shall have bonding bushing.
ELE14-00586 Final3/11/20143/12/20143/12/2014 9:17:38 AMACANC
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI needed temp pole inspection
ELE14-00586 Temporary Service3/12/20143/12/20143/12/2014 9:17:02 AMPFAIL
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI 250.24- AC service shal have a grounding electrode conductor connected to the grounded conductor at service disconnect. Wire not landed in lug.
ELE14-00193 Final3/11/20143/12/20143/12/2014 8:59:41 AMAPASS
Code for lock box is xxxx Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Final ok
GCE14-00031 GCE-Final3/11/20143/12/20143/12/2014 8:47:43 AMAPASS
Carlos ###-#### Final ok
GCE14-00031 GCE-Permanent Service3/12/20143/12/20143/12/2014 8:47:05 AMPPASS
Carlos ###-#### p/s o/h n ok
ELE14-00565 Electrical Rough-In3/11/20143/12/20143/11/2014 12:32:09 PMAPASS
Rick Brown Phone #: ###-#### 2nd floor offices divided. Wall rough in ok cover