ELE13-03552
| Final | 3/12/2014 | 3/12/2014 | 3/12/2014 3:09:50 PM | P | PASS |
|
|
Can you please call me ahead of time so I can make sure someone is there to let you in. Thanks mark Phone #: ###-#### >> Inspection requested via web by Mark Hennequin Final ok
|
ELE13-02057
| Electrical Rough-In | 3/12/2014 | 3/12/2014 | 3/12/2014 2:26:50 PM | P | PASS |
|
|
Robert. 3rd floor restroom rough-in. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy 1st floor apartment lobby walls and hard lid access panels will be needed for existing junction boxes and disconnects, 3rd floor bathrooms wall and hard lid rough in ok
|
ELE14-00588
| Final | 3/12/2014 | 3/12/2014 | 3/12/2014 1:15:23 PM | P | PASS |
|
|
Please provide a final inspection for the temporary power pole. Call Darrell with any questions. Thanks, Sean Phone #: ###-#### >> Inspection requested via web by Kevin Perez Temp pole final ok
|
ELE14-00588
| Temporary Service | 3/12/2014 | 3/12/2014 | 3/12/2014 1:15:10 PM | P | PASS |
|
|
Please provide a final inspection for the temporary power pole. Call Darrell with any questions. Thanks, Sean Phone #: ###-#### >> Inspection requested via web by Kevin Perez t/s o/h n ok
|
ELE14-00449
| Final | 3/11/2014 | 3/12/2014 | 3/12/2014 12:37:02 PM | A | PASS |
|
|
Please call Carlos if you have any questions. If no corrections please do a final Phone #: ###-#### >> Inspection requested via web by David Mackey Final ok
|
ELE14-00449
| Permanent Service | 3/12/2014 | 3/12/2014 | 3/12/2014 12:09:58 PM | P | PASS |
|
|
Please call Carlos if you have any questions. If no corrections please do a final Phone #: ###-#### >> Inspection requested via web by David Mackey p/s o/h n ok
|
ELE14-00157
| Electrical Rough-In | 3/11/2014 | 3/12/2014 | 3/12/2014 10:16:21 AM | A | PASS |
|
|
Ground work inspection. If you have any questions please contact Craig Timmons. Phone #: ###-#### >> Inspection requested via web by Vicki Moore North half under slab rough in ok cover
|
ELE14-00562
| Final | 3/12/2014 | 3/12/2014 | 3/12/2014 9:52:10 AM | A | PASS |
|
|
Rex The Homeowner said the back gate will be good for you to go thru. Final ok
Mike Phone #: ###-#### >> Inspection requested via web by Mike Cole
|
ELE14-00437
| Permanent Service | 3/11/2014 | 3/12/2014 | 3/12/2014 9:35:45 AM | A | FAIL |
|
|
Erin or Dean-Please call at least 30 mins in advance of inspection Phone #: 412- 0527 230.28- Where service mast is used as support for overhead swing and it extends 3' or more past its support it shall have additional support. 250.90(B)- Metal nipple ran through concentric knockout shall have bonding bushing.
|
ELE14-00586
| Final | 3/11/2014 | 3/12/2014 | 3/12/2014 9:17:38 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI needed temp pole inspection
|
ELE14-00586
| Temporary Service | 3/12/2014 | 3/12/2014 | 3/12/2014 9:17:02 AM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI 250.24- AC service shal have a grounding electrode conductor connected to the grounded conductor at service disconnect. Wire not landed in lug.
|
ELE14-00193
| Final | 3/11/2014 | 3/12/2014 | 3/12/2014 8:59:41 AM | A | PASS |
|
|
Code for lock box is xxxx Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Final ok
|
GCE14-00031
| GCE-Final | 3/11/2014 | 3/12/2014 | 3/12/2014 8:47:43 AM | A | PASS |
|
|
Carlos ###-#### Final ok
|
GCE14-00031
| GCE-Permanent Service | 3/12/2014 | 3/12/2014 | 3/12/2014 8:47:05 AM | P | PASS |
|
|
Carlos ###-#### p/s o/h n ok
|
ELE14-00565
| Electrical Rough-In | 3/11/2014 | 3/12/2014 | 3/11/2014 12:32:09 PM | A | PASS |
|
|
Rick Brown Phone #: ###-#### 2nd floor offices divided. Wall rough in ok cover
|