Inspections for the day of: Tuesday, March 12, 2019.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00756 Rough-in3/11/20193/12/20193/13/2019 3:19:38 PMAPASS
Phone #: ###-#### Inspection requested via web by Dave Sorensen
- R/I ok
- three toe kicks will need to be ducted out at final
- transfer air for bedrooms will need to be installed at final
MEC18-05106 Final3/12/20193/12/20193/12/2019 4:05:08 PMPPASS
lockbox code: 1369 by back door at hose bib
Man J and permit in kitchen drawer to right of sink. Phone #: ###-#### Inspection requested via web by Bryan Palmer
- final ok
MEC18-02635 Final3/6/20193/12/20193/12/2019 3:17:29 PMPNH
Please call when you are on your way Phone #: ###-#### Inspection requested via web by Andrea Grigsby
- no access to home left notice on front door
MEC19-00753 Final3/7/20193/12/20193/12/2019 2:51:43 PMPPASS
Please call the office in route ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout
- furnace ac coil ok
MEC19-00632 Final3/5/20193/12/20193/12/2019 2:18:51 PMPPASS
Please inspect after 1 PM. Homeowner Barbara Martin ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- final ok
MEC19-00955 Final3/11/20193/12/20193/12/2019 2:01:41 PMPFAIL
Please call Chuck on your way. - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- furnace ac coil co ok
- electrical permit needs pulled before mechanical permit gets finaled
MEC19-00961 Final3/8/20193/12/20193/12/2019 1:44:17 PMPPASS
INSTALLER BRANDAN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- furnace ac coil co ok
MEC19-00542 Final3/6/20193/12/20193/12/2019 1:43:56 PMPNH
Please inspect after 1 PM. Pablo Riojas ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
- no access to home left notice on front door
MEC19-00990 Pressure Test3/11/20193/12/20193/12/2019 1:26:27 PMPNR
PLEASE CALL HOMEOWNER SANDE WHEN IN ROUTE, LINE IS UNDER PRESSURE AND OUTSIDE ACCESS FOR GAS LINE Phone #: ###-#### Inspection requested via web by Rick Montgomery
MEC19-00898 Pressure Test3/11/20193/12/20193/12/2019 11:40:49 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves
- 20lb gas pressure test ok
-5lb flue pressure test ok
- tagged gas meter location
MEC19-00898 Rough-in3/11/20193/12/20193/12/2019 11:40:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves
- R/I ok
MEC19-00332 Final3/12/20193/12/20193/12/2019 11:24:30 AMAFAIL
Phone #: ###-#### Inspection requested via web by PATTY KIRK
- both regulators for unit heaters need to be vented to the outdoors
MEC19-00616 Final3/11/20193/12/20193/12/2019 11:15:46 AMANR
JAMES IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
- need to see condensate for mini split installed for final
MEC19-00616 Pressure Test3/11/20193/12/20193/12/2019 11:15:11 AMAPASS
JAMES IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER
- 60lb gas pressure test for one new RTU ok
MEC19-00468 Final3/11/20193/12/20193/12/2019 10:28:45 AMAFAIL
Phone #: ###-####
- furnace flue needs 1" clearanes
-flue needs insulation sheild in attic
- duct work needs supported in crawl
- need add gas line and duct work to permit
- water heater closet next to furnace needs to framed and will have to be air tight on bedroom side so combustion is taken from outdoors/ access door needs to be self closing and sealed with weatherstripping
- next inspection needs to be a R/I not a final
- house looks to be in the process of being remodeled
MEC19-00468 Pressure Test3/11/20193/12/20193/12/2019 10:25:30 AMAPASS
Phone #: ###-####
- 20lb gas pressure test ok
-tagged gas meter
MEC19-00967 Final3/11/20193/12/20193/12/2019 9:54:47 AMAPASS
Re- inspection. Garage code 0852 Phone #: ###-#### Inspection requested via web by Sheldon Lebow
- fireplace final ok
MEC19-00635 Final3/7/20193/12/20193/12/2019 9:46:23 AMAPASS
PLEASE CALL CONTRACTOR NATE @ # LISTED WHEN EN ROUTE Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING
- range hood ok
- final ok
MEC18-02774 Mec-Aging Inspection3/12/20193/12/20193/12/2019 9:38:48 AM DONE
no inspections have been schedule since pulling permit. Permit will expire in 180 days if not active
MEC18-02559 Final3/11/20193/12/20193/12/2019 9:36:59 AMANH
Inspection requested via web by Marisa Hone
- no access to home left notice on front door
MEC18-02779 Mec-Aging Inspection3/12/20193/12/20193/12/2019 9:18:45 AM DONE
Permit will expire in 180 if not active
MEC18-02236 Mec-Aging Inspection3/12/20193/12/20193/12/2019 9:16:55 AM DONE
Permit will expire in 180 days if not active
MEC18-03396 Final3/11/20193/12/20193/12/2019 9:13:35 AMAPASS
Chris Phone #: ###-####
- 5lb ok
- final ok