Inspections for the day of: Thursday, March 12, 2020.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02363 Final3/12/20203/12/20203/12/2020 2:32:48 PMPPASS
All units this building are ready 101-105 Phone #: ###-#### Inspection requested via web by Cevyn Recla Ok final units 101 and 102
ELE20-00862 Electrical Rough-In3/11/20203/12/20203/12/2020 1:59:39 PMPPASS
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Ok cover 1 wall suite 100
ELE19-00947 Electrical Rough-In3/12/20203/12/20203/12/2020 12:51:55 PMPPASS
andy Phone #: ###-#### Ok cover 2nd floor ceiling by elevator.
ELE20-00845 Conference3/11/20203/12/20203/12/2020 12:51:05 PMADONE
conference Phone #: ###-#### Inspection requested via web by Dan Hobdey Discussed install of new 400a service to feed 3 disconnects on side of home, and re-feed 3 existing panels on the interior.
ELE16-01189 Final3/11/20203/12/20203/12/2020 11:56:45 AMAFAIL
Taylor Phone #: ###-####
1. AC whips need THHN, romex used right now.
2. 2nd AC has non-rated outdoor wiring.
3. Identify neutrals as hot wires in AC disconnects, also max fuse for AC installed is 25a. A 30a brkr is installed right now.
4. No GFI protection in garage.
5. Spark rings needed in all backsplash locatations.
6. GFI protection needed on back of kitchen island facing living.
7. Weather proof on back patio cannot be on with kitchen appliance circuit.
8. All bedroom lights need GFI protection. Verify smoke detectors are on ARC fault circuit.
9. Boxes in bonus need cover plates and lights need installed a long with stairwell.
10. 14-3 in bonus above panel needs installed in a box with wire nuts and blanked off.
A licensed electrical contractor needs to be hired to complete all corrections. Posted notices on front window.
ELE19-02363 Final3/11/20203/12/20203/12/2020 10:51:21 AMAPASS
Looking for final on units 103, 104, and 105. Garage code 1268 Phone #: ###-#### Inspection requested via web by Cevyn Recla Units 103,104 and 105 Ok final
ELE20-00857 Electrical Rough-In3/11/20203/12/20203/12/2020 9:30:31 AMAPASS
Phone #: ###-#### Inspection requested via web by ron spen cer Ok cover bathroom
ELE16-00796 ELE-Aging Inspection3/12/20203/12/20203/12/2020 5:25:42 AM DONE
We spoke on the phone on 12/12/19, we need to get a final inspection scheduled for this address. Please coordinate with homeowner.