Inspections for the day of: Monday, March 13, 2000.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR99-00604 INSP-Sprinkler Rough-in3/13/20003/13/20003/13/2000 12:00:00 AM PART
walked throug the building with Trent - new soffits are being installed near kitchen - may cause overspacing.
FIR99-00602 INSP-Sprinkler Rough-in/Hydro3/13/20003/13/20003/13/2000 12:00:00 AMAPASS
Bldg 4 hydro completed on 3/10 - okay
FIR99-00602 INSP-Sprinkler Rough-in3/13/20003/13/20003/13/2000 12:00:00 AMAPART
rough-in okay. still requires tenting check before cover
BLD98-01409 FIRE-Conference3/13/20003/13/20003/13/2000 12:00:00 AMAPART
gave general the requirements for the stair signage UBC Standard 10-2
FIR99-00109 INSP-Sprinkler Rough-in/Hydro3/13/20003/13/20003/13/2000 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 03/13/2000 at 10:30:00. Contact: . Stand pipe and main riser hydro ok. 3/14/00 1:55:10 PM
BLD99-03094 FIRE-Final Inspection3/13/20003/13/20003/13/2000 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 03/13/2000 at 11:09:56. Contact: ###-####.