Inspections for the day of: Thursday, March 13, 2003.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00380 INSP-Final Inspection3/12/20033/13/20033/13/2003 12:00:00 AMAFAIL
###-#### dean The existing notification circuit still needs repaired. 3/13/2003 11:18:53 AM
FIR02-00512 INSP-Final Inspection3/12/20033/13/20033/13/2003 12:00:00 AMAFAIL
###-#### The 12 volt power supply #2 needs 26 ah batteries, need letter from Grinnell on verification of inspectors tests orfice size, provide verification on the knox key boxes are ok with the fire dept 3/13/2003 10:02:53 AM
FIR02-00423 INSP-Sprinkler Rough-in/Hydro3/12/20033/13/20033/13/2003 12:00:00 AMAPART
sprinkler piping is ok to cover in rooms marked on the job site approved plans. Upright sprinkler heads to be added above the mens restroom 3/13/2003 1:36:49 PM
BLD02-02639 FIRE-Final Inspection3/12/20033/13/20033/13/2003 12:00:00 AMAPASS
bob- ###-#### Fire life safety finaled 3/13/2003 10:28:52 AM
BLD02-02924 FIRE-Final Inspection3/13/20033/13/20033/13/2003 12:00:00 AMPFAIL
###-#### Could not perform a final inspection due to fire alarm plans not having been resubmitted due to the two duct smoke detectors. I spoke with the contractor about live safety requirements 3/13/2003 3:07:28 PM
FIR02-00385 INSP-Conference3/11/20033/13/20033/13/2003 12:00:00 AMPPART
Inspection was for the testing of the fire pump. Russ with Nickerson pump was present to perform the test 3/13/2003 3:26:55 PM