Inspections for the day of: Monday, March 13, 2006.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01669 FIRE-Final Inspection3/13/20063/13/20063/13/2006 4:55:34 PMPPASS
The project related alarm and sprinkler have been approved, fire life safety finaled.
BLD05-01077 FIRE-Final Inspection3/10/20063/13/20063/13/2006 4:52:26 PMPNR
The project related alarm and sprinkler must be approved prior to life safety final.
FIR05-00425 INSP-Final Inspection3/13/20063/13/20063/13/2006 4:51:27 PMPFAIL
Provide functional alarm pressure switch at the third floor dry system, repair air compressor at the third floor, provide annual tags on risers, repair stop button at pump controller, secure drum drip assemblies to structure, perform final walkthrough for dry systems code compliance.
FIR05-00695 INSP-Final Inspection3/10/20063/13/20063/13/2006 4:44:58 PMAFAIL
Third floor alarm pressure switch at the dry system failed to reset, low air at the ground level garage dry system adjusted while on site, signal verification list to be faxed in, requested date on batteries at panel. Tested third, second, ground level garage floors, stair 4 elevator, stair 4 and 3 alarm and notification devices, tested pump room, command center, and fire rated corridor alarm/notification/trouble and supervisory conditions, verified items on previous c/n have been completed for the generator room.
FIR05-00564 INSP-Final Inspection3/10/20063/13/20063/13/2006 12:27:20 PMAFAIL
The required approved plans were not made available for inspection.
FIR05-00426 INSP-Final Inspection3/10/20063/13/20063/13/2006 12:25:46 PMAFAIL
Two 180 cd strobes as shown on approved plans are not installed at the patio dining area, will need to install and test for functionality at next inspection. The remainder of items on c/n have been completed including resubmitted plans, EOL changes, added and relocated devices shown on approved plans, final pending test of 180 cd strobe notification devices.
FIR05-00684 INSP-Final Inspection3/10/20063/13/20063/13/2006 12:15:29 PMAPASS
Shell alarm permit is complete, TI alarm finaled.
FIR05-00685 INSP-Final Inspection3/10/20063/13/20063/13/2006 12:14:27 PMAPASS
Shell alarm permit is complete, TI alarm finaled.
FIR05-00531 INSP-Final Inspection3/10/20063/13/20063/13/2006 12:13:40 PMAPASS
Shell alarm permit is complete, TI alarm finaled.
FIR05-00666 INSP-Final Inspection3/10/20063/13/20063/13/2006 12:12:05 PMAPASS
Shell alarm permit is complete, TI alarm finaled.
FIR05-00646 INSP-Final Inspection3/10/20063/13/20063/13/2006 12:10:29 PMAPASS
Shell alarm permit is complete, TI alarm finaled.
FIR05-00623 INSP-Final Inspection3/10/20063/13/20063/13/2006 12:09:16 PMAPASS
Shell alarm permit is now complete, TI alarm finaled.
FIR05-00076 INSP-Final Inspection3/10/20063/13/20063/13/2006 12:07:08 PMAPASS
Required items on the correction notice have been completed, shell and core fire alarm permit finaled.
BLD05-02346 FIRE-Final Inspection3/10/20063/13/20063/13/2006 10:49:13 AMAPASS
The project related fire sprinkler permit work has been approved and finaled, c/n items are complete, life safety acceptable.
FIR06-00060 INSP-Final Inspection3/13/20063/13/20063/13/2006 10:46:25 AMAPASS
Escutcheons have been installed, drop ceiling is in place, fire sprinkler permit finaled.
FIR05-00583 INSP-Final Inspection3/10/20063/13/20063/13/2006 10:40:23 AMAPASS
Three items defficient were corrected while on site (missing hanger, painted SW head and standard response head in closet), fire sprinkler permit work passed inspection.
FIR06-00125 INSP-Final Inspection3/10/20063/13/20063/13/2006 10:36:00 AMAPASS
Fire alarm permit finaled.
FIR05-00174 INSP-Final Inspection3/10/20063/13/20063/13/2006 12:00:00 AMPCANC
kenny; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wrong address