BLD05-01669
| FIRE-Final Inspection | 3/13/2006 | 3/13/2006 | 3/13/2006 4:55:34 PM | P | PASS |
|
|
The project related alarm and sprinkler have been approved, fire life safety finaled.
|
BLD05-01077
| FIRE-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 4:52:26 PM | P | NR |
|
|
The project related alarm and sprinkler must be approved prior to life safety final.
|
FIR05-00425
| INSP-Final Inspection | 3/13/2006 | 3/13/2006 | 3/13/2006 4:51:27 PM | P | FAIL |
|
|
Provide functional alarm pressure switch at the third floor dry system, repair air compressor at the third floor, provide annual tags on risers, repair stop button at pump controller, secure drum drip assemblies to structure, perform final walkthrough for dry systems code compliance.
|
FIR05-00695
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 4:44:58 PM | A | FAIL |
|
|
Third floor alarm pressure switch at the dry system failed to reset, low air at the ground level garage dry system adjusted while on site, signal verification list to be faxed in, requested date on batteries at panel. Tested third, second, ground level garage floors, stair 4 elevator, stair 4 and 3 alarm and notification devices, tested pump room, command center, and fire rated corridor alarm/notification/trouble and supervisory conditions, verified items on previous c/n have been completed for the generator room.
|
FIR05-00564
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 12:27:20 PM | A | FAIL |
|
|
The required approved plans were not made available for inspection.
|
FIR05-00426
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 12:25:46 PM | A | FAIL |
|
|
Two 180 cd strobes as shown on approved plans are not installed at the patio dining area, will need to install and test for functionality at next inspection. The remainder of items on c/n have been completed including resubmitted plans, EOL changes, added and relocated devices shown on approved plans, final pending test of 180 cd strobe notification devices.
|
FIR05-00684
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 12:15:29 PM | A | PASS |
|
|
Shell alarm permit is complete, TI alarm finaled.
|
FIR05-00685
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 12:14:27 PM | A | PASS |
|
|
Shell alarm permit is complete, TI alarm finaled.
|
FIR05-00531
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 12:13:40 PM | A | PASS |
|
|
Shell alarm permit is complete, TI alarm finaled.
|
FIR05-00666
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 12:12:05 PM | A | PASS |
|
|
Shell alarm permit is complete, TI alarm finaled.
|
FIR05-00646
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 12:10:29 PM | A | PASS |
|
|
Shell alarm permit is complete, TI alarm finaled.
|
FIR05-00623
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 12:09:16 PM | A | PASS |
|
|
Shell alarm permit is now complete, TI alarm finaled.
|
FIR05-00076
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 12:07:08 PM | A | PASS |
|
|
Required items on the correction notice have been completed, shell and core fire alarm permit finaled.
|
BLD05-02346
| FIRE-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 10:49:13 AM | A | PASS |
|
|
The project related fire sprinkler permit work has been approved and finaled, c/n items are complete, life safety acceptable.
|
FIR06-00060
| INSP-Final Inspection | 3/13/2006 | 3/13/2006 | 3/13/2006 10:46:25 AM | A | PASS |
|
|
Escutcheons have been installed, drop ceiling is in place, fire sprinkler permit finaled.
|
FIR05-00583
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 10:40:23 AM | A | PASS |
|
|
Three items defficient were corrected while on site (missing hanger, painted SW head and standard response head in closet), fire sprinkler permit work passed inspection.
|
FIR06-00125
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 10:36:00 AM | A | PASS |
|
|
Fire alarm permit finaled.
|
FIR05-00174
| INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 12:00:00 AM | P | CANC |
|
|
kenny; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wrong address
|