Inspections for the day of: Monday, March 13, 2006.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorWilliam E Thomas
TitleELE-INSPECTOR
Phone #794-9492
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00850 Permanent Service3/13/20063/13/20063/13/2006 5:13:36 PMPFAIL
tom wilson ###-####

grounding electrode conductor not on neutral buss.
ELE06-00394 Final3/12/20063/13/20063/13/2006 4:34:39 PMPPASS
Scheduled by a contractor via Hello! on 3/12/2006 at 8:52:06 PM. Contact: ###-####.
ELE06-00805 Electrical Rough-In3/13/20063/13/20063/13/2006 4:33:54 PMPPASS
need final on ufer ground. Internet Inspection Request from: Andy Rose
ok to cover the concrete for the ufer
ELE06-00827 Final3/13/20063/13/20063/13/2006 4:17:04 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
ELE06-00231 Rough-In Permanent Service3/13/20063/13/20063/13/2006 4:14:30 PMPCANC
Dennis; Phone #: ###-####
ELE06-00231 Conference3/13/20063/13/20063/13/2006 2:18:32 PMPCANC
dennis; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
still working on correc\tions, talked about the meaning of 250.104. cancelled per inspector reschuled for permanent service instead 3:00 pm
ELE06-00231 Permanent Service3/13/20063/13/20063/13/2006 12:00:00 AMPPASS
Dennis; Phone #: ###-####
p/s u/g n ok
ELE06-00827 Rough-In Permanent Service3/13/20063/13/20063/13/2006 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
p/s o/h reconnect ok
bonding and grounding ok, inside work of each apartment needs yo be looked at.