Inspections for the day of: Tuesday, March 13, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04325 Electrical Rough-In3/13/20073/13/20073/13/2007 4:04:18 PMPFAIL
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall met elect, no tie wires for ceiling fixtures and low voltage wire on grid, did not want corr notice written, said would fix and recall
ELE07-00008 Final3/13/20073/13/20073/13/2007 3:29:16 PMPPASS
Candy pls call prior for lock box code other number (###-####); Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok to final
ELE07-00800 Conference3/13/20073/13/20073/13/2007 2:37:12 PMPDONE
auther; Phone #: ###-#### Internet Inspection Request from: Victoria Beall talked about power and probably best to add temp pole, and some of new service items such as grounding and mast and circuiting
ELE07-00832 Electrical Rough-In3/13/20073/13/20073/13/2007 1:49:18 PMPPASS
STU; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ri piping and wiring ok, will call for final
ELE07-00637 Final3/12/20073/13/20073/13/2007 1:47:58 PMPPASS
Phone #: ###-#### corr made, ok to final
ELE07-00637 Permanent Service3/13/20073/13/20073/13/2007 12:53:14 PMPPASS
Phone #: ###-#### p/s o/h rec ok, see final
ELE07-00840 Final3/13/20073/13/20073/13/2007 12:36:47 PMPPASS
steve-- ###-#### cell--on the north & south side of building u/g ok, called contr to add 1 cnd strap, ok to final
ELE05-02720 Final3/12/20073/13/20073/13/2007 10:44:04 AMAFAIL
steve; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met owner, left corr notice, nec 210.8(A)(2) garage recpts shall be gfci, 210.8(A)(7) laundry recpt shall be gfci, 422.31(B) water heater shall have disconnect provisions, BCC floor recpt shall have steel cover, garage shall have minimum 3' clearance around walls for access to inspect
ELE06-01074 Final3/12/20073/13/20073/13/2007 9:56:07 AMAFAIL
eil ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith met owner, left corr notice, nec 408.4 circuit directory shall be clear, concise, and complete and permanent labelled, 406.5 recpt faceplates shall seat against mounting surface, 210.8(A)(2) garage recpts shall be gfci protected
ELE07-00819 Electrical Rough-In3/12/20073/13/20073/13/2007 9:16:30 AMAPART
Contact: TJ Dyer PLEASE CALL BEFORE GOING FOR INSPECTION.
Conduit inspection only. Phone #: ###-#### u/g conduit from house to garages only ok to cover
ELE07-00663 Conference3/12/20073/13/20073/13/2007 8:52:58 AMADONE
Please consult with Jim on confirming grounding requirements and possible explosion proofing needed. thanks Phone #: ###-#### talked about grounding, no seal-offs look to be req'd, service discussion, common gec ok for gen and xfmr
ELE07-00824 Electrical Rough-In3/12/20073/13/20073/13/2007 8:05:15 AMAPASS
Phone #: ###-#### walls only ok to cover