ELE05-04325
| Electrical Rough-In | 3/13/2007 | 3/13/2007 | 3/13/2007 4:04:18 PM | P | FAIL |
|
|
jason; Phone #: ###-#### Internet Inspection Request from: Victoria Beall met elect, no tie wires for ceiling fixtures and low voltage wire on grid, did not want corr notice written, said would fix and recall
|
ELE07-00008
| Final | 3/13/2007 | 3/13/2007 | 3/13/2007 3:29:16 PM | P | PASS |
|
|
Candy pls call prior for lock box code other number (###-####); Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok to final
|
ELE07-00800
| Conference | 3/13/2007 | 3/13/2007 | 3/13/2007 2:37:12 PM | P | DONE |
|
|
auther; Phone #: ###-#### Internet Inspection Request from: Victoria Beall talked about power and probably best to add temp pole, and some of new service items such as grounding and mast and circuiting
|
ELE07-00832
| Electrical Rough-In | 3/13/2007 | 3/13/2007 | 3/13/2007 1:49:18 PM | P | PASS |
|
|
STU; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ri piping and wiring ok, will call for final
|
ELE07-00637
| Final | 3/12/2007 | 3/13/2007 | 3/13/2007 1:47:58 PM | P | PASS |
|
|
Phone #: ###-#### corr made, ok to final
|
ELE07-00637
| Permanent Service | 3/13/2007 | 3/13/2007 | 3/13/2007 12:53:14 PM | P | PASS |
|
|
Phone #: ###-#### p/s o/h rec ok, see final
|
ELE07-00840
| Final | 3/13/2007 | 3/13/2007 | 3/13/2007 12:36:47 PM | P | PASS |
|
|
steve-- ###-#### cell--on the north & south side of building u/g ok, called contr to add 1 cnd strap, ok to final
|
ELE05-02720
| Final | 3/12/2007 | 3/13/2007 | 3/13/2007 10:44:04 AM | A | FAIL |
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met owner, left corr notice, nec 210.8(A)(2) garage recpts shall be gfci, 210.8(A)(7) laundry recpt shall be gfci, 422.31(B) water heater shall have disconnect provisions, BCC floor recpt shall have steel cover, garage shall have minimum 3' clearance around walls for access to inspect
|
ELE06-01074
| Final | 3/12/2007 | 3/13/2007 | 3/13/2007 9:56:07 AM | A | FAIL |
|
|
eil ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith met owner, left corr notice, nec 408.4 circuit directory shall be clear, concise, and complete and permanent labelled, 406.5 recpt faceplates shall seat against mounting surface, 210.8(A)(2) garage recpts shall be gfci protected
|
ELE07-00819
| Electrical Rough-In | 3/12/2007 | 3/13/2007 | 3/13/2007 9:16:30 AM | A | PART |
|
|
Contact: TJ Dyer PLEASE CALL BEFORE GOING FOR INSPECTION. Conduit inspection only. Phone #: ###-#### u/g conduit from house to garages only ok to cover
|
ELE07-00663
| Conference | 3/12/2007 | 3/13/2007 | 3/13/2007 8:52:58 AM | A | DONE |
|
|
Please consult with Jim on confirming grounding requirements and possible explosion proofing needed. thanks Phone #: ###-#### talked about grounding, no seal-offs look to be req'd, service discussion, common gec ok for gen and xfmr
|
ELE07-00824
| Electrical Rough-In | 3/12/2007 | 3/13/2007 | 3/13/2007 8:05:15 AM | A | PASS |
|
|
Phone #: ###-#### walls only ok to cover
|