FIR06-00620
| FIR-Aging Inspection | 3/13/2007 | 3/13/2007 | 3/16/2007 4:16:14 PM | | DONE |
|
|
work in progress
|
BLD06-03241
| FIRE-Final Inspection | 3/13/2007 | 3/13/2007 | 3/13/2007 5:59:43 PM | P | NR |
|
|
Scheduled for 3/14
|
FIR06-00800
| INSP-Sprinkler Rough-in/Hydro | 3/13/2007 | 3/13/2007 | 3/13/2007 5:56:29 PM | P | DEFR |
|
|
To be completed 3/14
|
FIR07-00033
| INSP-Supply line flush | 3/13/2007 | 3/13/2007 | 3/13/2007 5:53:53 PM | P | PART |
|
|
UG supply line flush performed satisfactory.
|
FIR05-00402
| INSP-Sprinkler Rough-in/Hydro | 3/12/2007 | 3/13/2007 | 3/13/2007 5:52:22 PM | P | NR |
|
|
Per phone call from contractor, system is not ready for inspection.
|
FIR06-00800
| INSP-Supply line flush | 3/13/2007 | 3/13/2007 | 3/13/2007 1:42:54 PM | P | PART |
|
|
UG fire supply line flush completed.
|
FIR07-00138
| INSP-Final Inspection | 3/12/2007 | 3/13/2007 | 3/13/2007 1:18:30 PM | A | PART |
|
|
Noted correction items from the previous field inspection have been completed, need to review approved TI fire alarm plans, provide as-built plans for field mods, and check nac extender panel for this circut.
|
FIR06-00595
| INSP-Final Inspection | 3/12/2007 | 3/13/2007 | 3/13/2007 12:40:15 PM | A | FAIL |
|
|
Re-inspection for the 4th floor corrections failed due to non-functional SD in the telephone and electrical rooms, and inadequate audibility for the SS notification devices.
|
FIR06-00766
| INSP-Sprinkler Rough-in/Hydro | 3/12/2007 | 3/13/2007 | 3/13/2007 12:34:45 PM | A | PART |
|
|
OH fire sprinkler inspection for the remainder of the cleanroom expansion and lab room 105 completed. Note, rough-in inspections to be requested and finished prior to ceiling cover. Two heads in the corridor shown to be added are not yet installed.
|
FIR06-00512
| INSP-Final Inspection | 3/12/2007 | 3/13/2007 | 3/13/2007 10:57:29 AM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD06-02402
| FIRE-Final Inspection | 3/12/2007 | 3/13/2007 | 3/13/2007 10:17:42 AM | A | PART |
|
|
Final fire life safety pending completion of the modifications for the fire sprinkler system, okay for temp. occupancy per conditions indicated in the meeting notes.
|
BLD06-03241
| FIRE-Final Inspection | 3/12/2007 | 3/13/2007 | 3/13/2007 10:12:57 AM | A | FAIL |
|
|
Repair one exit sign, provide approved door hardware at the back office and shop exits, one additional extinguisher will be required in the shop area.
|
FIR07-00214
| INSP-Final Inspection | 3/13/2007 | 3/13/2007 | 3/13/2007 9:41:59 AM | A | PASS |
|
|
Fire sprinkler work passed field inspection, permit finaled.
|