Inspections for the day of: Tuesday, March 13, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00620 FIR-Aging Inspection3/13/20073/13/20073/16/2007 4:16:14 PM DONE
work in progress
BLD06-03241 FIRE-Final Inspection3/13/20073/13/20073/13/2007 5:59:43 PMPNR
Scheduled for 3/14
FIR06-00800 INSP-Sprinkler Rough-in/Hydro3/13/20073/13/20073/13/2007 5:56:29 PMPDEFR
To be completed 3/14
FIR07-00033 INSP-Supply line flush3/13/20073/13/20073/13/2007 5:53:53 PMPPART
UG supply line flush performed satisfactory.
FIR05-00402 INSP-Sprinkler Rough-in/Hydro3/12/20073/13/20073/13/2007 5:52:22 PMPNR
Per phone call from contractor, system is not ready for inspection.
FIR06-00800 INSP-Supply line flush3/13/20073/13/20073/13/2007 1:42:54 PMPPART
UG fire supply line flush completed.
FIR07-00138 INSP-Final Inspection3/12/20073/13/20073/13/2007 1:18:30 PMAPART
Noted correction items from the previous field inspection have been completed, need to review approved TI fire alarm plans, provide as-built plans for field mods, and check nac extender panel for this circut.
FIR06-00595 INSP-Final Inspection3/12/20073/13/20073/13/2007 12:40:15 PMAFAIL
Re-inspection for the 4th floor corrections failed due to non-functional SD in the telephone and electrical rooms, and inadequate audibility for the SS notification devices.
FIR06-00766 INSP-Sprinkler Rough-in/Hydro3/12/20073/13/20073/13/2007 12:34:45 PMAPART
OH fire sprinkler inspection for the remainder of the cleanroom expansion and lab room 105 completed. Note, rough-in inspections to be requested and finished prior to ceiling cover. Two heads in the corridor shown to be added are not yet installed.
FIR06-00512 INSP-Final Inspection3/12/20073/13/20073/13/2007 10:57:29 AMAPASS
Fire sprinkler permit finaled.
BLD06-02402 FIRE-Final Inspection3/12/20073/13/20073/13/2007 10:17:42 AMAPART
Final fire life safety pending completion of the modifications for the fire sprinkler system, okay for temp. occupancy per conditions indicated in the meeting notes.
BLD06-03241 FIRE-Final Inspection3/12/20073/13/20073/13/2007 10:12:57 AMAFAIL
Repair one exit sign, provide approved door hardware at the back office and shop exits, one additional extinguisher will be required in the shop area.
FIR07-00214 INSP-Final Inspection3/13/20073/13/20073/13/2007 9:41:59 AMAPASS
Fire sprinkler work passed field inspection, permit finaled.