Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-02158 FIRE-Final Inspection3/11/20083/12/2008 A 
FIR07-00710 INSP-Final Inspection3/10/20083/13/20083/14/2008 1:18:49 PMAPART
Completed new fire alarm system testing for the networked panel, interconnection to building one, phase two sprinkler system monitoring, notification appliances for the basement parking garage, and elevator monitoring/recall. Common corridors and apartment units not tested at this time, noted wall mounted horn locations are not in compliance with NFPA 72 2002 7.4.6.1- see also fire code review note #28, elevator fire doors at some floors are not adjusted or missing smoke seals, the main entry door mag locks failed to drop out on alarm condition.
BLD07-02748 FIRE-Final Inspection3/13/20083/13/20083/13/2008 2:33:51 PMPNR
Inspection intended to be scheduled for 3/14 per contractor, not ready for final at this time.
BLD07-02747 FIRE-Final Inspection3/13/20083/13/20083/13/2008 2:30:11 PMPNR
Missing fire extinguishers at some locations per contractor.
BLD06-03307 FIRE-Final Inspection3/11/20083/13/20083/13/2008 1:36:27 PMPNR
jose Phone #: ###-####
FIR08-00169 INSP-Final Inspection3/13/20083/13/20083/13/2008 1:35:51 PMPFAIL
Demo work has been completed, however two small restrooms and one electrical closet at the south side of the scope of work are to remain and will still require sprinkler coverage.
FIR08-00192 INSP-Sprinkler Rough-in/Hydro3/13/20083/13/20083/13/2008 1:32:56 PMPFAIL
Installation of the new wall has created an unprotected pocket at the west office, also need to remove ceiling tile for rough-in inspection of work at the east office.
FIR08-00169 INSP-Final Inspection3/12/20083/13/20083/13/2008 12:48:37 PMACANC
brandon Phone #: ###-#### Inspection cancelled from web by: Jeff Packham
BLD06-00076 BLD-Final3/13/20083/13/20083/13/2008 12:13:45 PMPFAIL
Need to repair ceiling adjacent to the smoke detector at the riser room, missing required lane marking at the fire dept. access road, incomplete address at one apartment unit, the project related fire sprinkler permit work has failed final inspection.
FIR07-00235 INSP-Final Inspection3/12/20083/13/20083/13/2008 12:07:34 PMAFAIL
The leak at the riser supply piping has not been repaired, discovered an additional leak at a closet sprinkler head in one apartment unit, travel cap at one ssu in a mechanical closet has not been removed, one defective pendent at a stairway needs replaced, missing escutcheon at one DSW, noted two additional painted heads in need of replacement including a DSW and one pendent at a stairway. Recommend contractor to perform a complete walkthrough of the project prior to scheduling a final inspection. Re-inspection fees will apply to the next field visit for project final.
FIR07-00236 INSP-Final Inspection3/12/20083/13/20083/13/2008 11:42:10 AMAPASS
Previous c/n items are complete, two painted heads replaced while on site, fire sprinkler permit finaled.
FIR06-00889 INSP-Final Inspection3/12/20083/13/20083/13/2008 11:40:44 AMAPASS
Incorrect device addresses at unit 102 amended while on site, relocated smoke alarms are acceptable, fire alarm work passed field testing, permit finaled.
FIR06-00888 INSP-Final Inspection3/12/20083/13/20083/13/2008 11:34:07 AMAPASS
Correction notice items verified for compliance, fire alarm final testing passed, permit finaled.
BLD06-00075 FIRE-Final Inspection3/12/20083/13/20083/13/2008 11:32:42 AMAFAIL
Provide fire dept. access lane marking per fire code review notes, noted painted and covered fire sprinkler heads at various locations to be replaced prior to final.
BLD07-03089 FIRE-Final Inspection3/13/20083/13/20083/13/2008 11:26:52 AMAPASS
Corrections verified for completion, fire life safety inspection passed.
FIR07-00710 INSP-Supply line flush3/10/20083/13/20083/13/2008 12:00:00 AMACANC