Inspections for the day of: Thursday, March 13, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00193 INSP-Sprinkler Rough-in3/12/20143/13/20143/13/2014 3:25:25 PMPPASS
See the city approved plans for location where piping can be covered with todays date.
FIR13-00558 INSP-Final Inspection3/13/20143/13/20143/13/2014 3:09:20 PMPPASS
Permit finaled
BLD13-02397 FIRE-Final Inspection3/12/20143/13/20143/13/2014 3:09:02 PMPPASS
Life safety passed. Need to provide ADA hardware on the pocket door.
FIR13-00697 INSP-Sprinkler Rough-in3/12/20143/13/20143/13/2014 2:13:13 PMAPASS
The remaining piping in the Patient Area is ok to cover. Rough-in passed for the OR area as far as mains/branchlines/hangers/seismic restraint. Will still need rough-in once the drops are cut.
FIR14-00054 INSP-Sprinkler Rough-in/Hydro3/7/20143/13/20143/13/2014 2:09:30 PMAFAIL
No city approved plans on site, if shop drawings match city approved resumittal are required showing the changes. Smoke detectors are too close to grills, candellas on strobes are not set correctly, strobes are overspace even if set correctly. FACP has been relocated. Manual pull station has been relocated. No test form provided. No sigal report provided. No test was performed.