ELE13-02121
| ELE-Aging Inspection | 3/13/2017 | 3/13/2017 | 3/16/2017 2:09:13 PM | | PASS |
|
|
Called John, He will drive by and check on job.
|
ELE17-00624
| Electrical Rough-In | 3/10/2017 | 3/13/2017 | 3/13/2017 3:54:20 PM | P | PASS |
|
|
Jason is the contact his cell no is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates 2nd floor north and south areas wall rough in cover
|
ELE16-01667
| Permanent Service | 3/13/2017 | 3/13/2017 | 3/13/2017 3:54:06 PM | P | FAIL |
|
|
Firepump service. 695.4- Overcurrent device shall carry indefinately locked rotor current. 400 installed 500 amp min. Contractor to change to 600 amp knife switch. 695.6- Wiring method to jockey pump shall be one listed, standard MC cable not listed.
|
ELE17-00638
| Electrical Rough-In | 3/13/2017 | 3/13/2017 | 3/13/2017 3:23:32 PM | P | PASS |
|
|
Wall Rough-In Inspection for level 13 restrooms. Contact Jon Novak Phone #: ###-#### Inspection requested via web by Cathy Duchek Area noted wall rough in ok cover
|
ELE17-00583
| Final | 3/10/2017 | 3/13/2017 | 3/13/2017 12:55:32 PM | A | FAIL |
|
|
We will not be onsite. Please call if you have any questions. Thank you. Phone #: ###-#### Inspection requested via web by Kelly Tarter 110.24- Available fault current shall be posted. 210.64- A 15 or 20 amp 120 volt receptacle outlet shall be located within 50' of service. 250.28(C)- Main bonding jumper screw not tight.
|
ELE16-01667
| Permanent Service | 3/10/2017 | 3/13/2017 | 3/13/2017 10:08:29 AM | A | PASS |
|
|
Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Fire pump service not included. 30 single phase meters, 2 3 phase meters. p/s u/g n ok
|
ELE17-00573
| Electrical Rough-In | 3/10/2017 | 3/13/2017 | 3/13/2017 9:25:38 AM | A | PASS |
|
|
Phone #: ###-#### Old garage has 50 amp circuit, informed 2nd range location not allowed on single family dwelling. Garage and laundry addition rough in ok cover
|
ELE17-00573
| Permanent Service | 3/13/2017 | 3/13/2017 | 3/13/2017 9:21:50 AM | P | PASS |
|
|
Phone #: ###-#### p/s u/g n ok
|
ELE16-02785
| Final | 3/10/2017 | 3/13/2017 | 3/13/2017 8:51:01 AM | A | PASS |
|
|
Garage code is 3358 Phone #: ###-#### Inspection requested via web by Dustin Kuester Front of cabinet removeable for hood receptacle for disconnect. Final ok
|