Inspections for the day of: Monday, March 13, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02121 ELE-Aging Inspection3/13/20173/13/20173/16/2017 2:09:13 PM PASS
Called John, He will drive by and check on job.
ELE17-00624 Electrical Rough-In3/10/20173/13/20173/13/2017 3:54:20 PMPPASS
Jason is the contact his cell no is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
2nd floor north and south areas wall rough in cover
ELE16-01667 Permanent Service3/13/20173/13/20173/13/2017 3:54:06 PMPFAIL
Firepump service.
695.4- Overcurrent device shall carry indefinately locked rotor current. 400 installed 500 amp min. Contractor to change to 600 amp knife switch.
695.6- Wiring method to jockey pump shall be one listed, standard MC cable not listed.
ELE17-00638 Electrical Rough-In3/13/20173/13/20173/13/2017 3:23:32 PMPPASS
Wall Rough-In Inspection for level 13 restrooms.
Contact Jon Novak Phone #: ###-#### Inspection requested via web by Cathy Duchek
Area noted wall rough in ok cover
ELE17-00583 Final3/10/20173/13/20173/13/2017 12:55:32 PMAFAIL
We will not be onsite. Please call if you have any questions. Thank you. Phone #: ###-#### Inspection requested via web by Kelly Tarter
110.24- Available fault current shall be posted.
210.64- A 15 or 20 amp 120 volt receptacle outlet shall be located within 50' of service.
250.28(C)- Main bonding jumper screw not tight.
ELE16-01667 Permanent Service3/10/20173/13/20173/13/2017 10:08:29 AMAPASS
Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Fire pump service not included.
30 single phase meters, 2 3 phase meters. p/s u/g n ok
ELE17-00573 Electrical Rough-In3/10/20173/13/20173/13/2017 9:25:38 AMAPASS
Phone #: ###-#### Old garage has 50 amp circuit, informed 2nd range location not allowed on single family dwelling. Garage and laundry addition rough in ok cover
ELE17-00573 Permanent Service3/13/20173/13/20173/13/2017 9:21:50 AMPPASS
Phone #: ###-#### p/s u/g n ok
ELE16-02785 Final3/10/20173/13/20173/13/2017 8:51:01 AMAPASS
Garage code is 3358 Phone #: ###-#### Inspection requested via web by Dustin Kuester
Front of cabinet removeable for hood receptacle for disconnect. Final ok